Operation
Azbil Corporation
2-34
Model SLX 110/120 - Smart displacement type level transmitter
Step
Button
Procedure
SFC screen
2
H
NEXT
or
L
PREV
press [NEXT] or [PREV] to go to the
torque tube temperature reading screen.
SLX CONFIG
TQTUBE TEMP ?
3
ENTER
( Yes )
NON-VOL
Press [ENTER].
TQTUBE TEMP
WORKING...
4
CLR
( No )
Displays the current torque tube
temperature.
Updated approximately every 6
seconds.
Pressing [CLR] twice sets the mode
back to the “Please perform next
operation” state.
TQTUBE TEMP
152.3 C