Operation
Azbil Corporation
2-54
Model SLX 110/120 - Smart displacement type level transmitter
Maintenance printout
This is a function to print out the internal data (tag No., damping time constant,
output range, input value, output value, etc....)of this instrument.
Can be used to record such things as the setting condition and fault condition of this
instrument.
Procedure
Maintenance printout is performed using the following procedure.
This operation can also be performed during measurement.
Step
Button
Procedure
SFC screen
1
CLR
( No )
Press [CLR] until the screen to the
right appears.
SLX TAG - 0001
READY...
2
SHIFT
Press [SHIFT].
SHIFT-
3
P
9
Press [9].
- Printing starts.
SLX TAG - 0001
WORKING...
i
PRINTING...
4
CLR
( No )
To stop printing, press [CLR].
SLX TAG - 0001
READY...