![Azbil SLX 110 User Manual Download Page 135](http://html1.mh-extra.com/html/azbil/slx-110/slx-110_user-manual_3042728135.webp)
Azbil Corporation
Maintenance
Model SLX 110/120 - Smart displacement type level transmitter 3-15
Step
Button
Procedure
SFC screen
3
Z
0
ACT PR
Enter zero [0] as the LRV using
numeric keys.
Example: [0]
LRV TAG - 0001
0_ mm
4
ENTER
( Yes )
NON-VOL
Press [ENTER].
LRV TAG - 0001
WORKING...
5
The LRV is set to 0 mm.
LRV TAG - 0001
0.0000 mm
6
COR- K
RECT
RESET
Press [CORRECT].
LRV TAG - 0001
ZERO INPUT ?
7
ENTER
( Yes )
NON-VOL
Press [ENTER]. A confirmation screen
will appear.
LRV TAG - 0001
ARE YOU SURE ?
8
ENTER
( Yes )
NON-VOL
After checking that the weight is not
swaying, press [ENTER] again.
LRV TAG - 0001
WORKING...
9
Setting of LRV completed
LRV TAG - 0001
LRV CORRECTED !
o
Calibrate URV.
Step
Button
Procedure
SFC screen
1
Apply 0% calibrated load to the torque
arm.
SLX TAG - 0001
READY...
2
URV F
100%
Press [URV]. The current URV will
appear. Example: 300.1 mm
URV TAG - 0001
300.1 mm
Summary of Contents for SLX 110
Page 1: ...Smart Displacement type Level Transmitter Model SLX 110 120 User s Manual CM2 SLX100 2001...
Page 4: ......
Page 8: ...iv Model SLX 110 120 Smart displacement type level transmitter...
Page 120: ...Operation Azbil Corporation 2 80 Model SLX 110 120 Smart displacement type level transmitter...
Page 150: ...Maintenance Azbil Corporation 3 30 Model SLX 110 120 Smart displacement type level transmitter...
Page 162: ...Azbil Corporation 5 2 Model SLX 110 120 Smart displacement type level transmitter...
Page 163: ......
Page 166: ......
Page 168: ......