Model SLX 110/120 - Smart displacement type level transmitter 2-69
Cancellation of constant current source mode
Step
Button
Procedure
SFC screen
1
OUT- J
PUT
INPUT
Press [OUTPUT].
OUTPUT TAG-0001
WORKING...
2
The current output data will appear.
Example: 50.0%
OUTPUT TAG-0001
50_ % #
3
CLR
( No )
Immediately, press [CLR].
OUTPUT TAG-0001
WORKING...
4
The system has recovered from the
constant current source mode.
The “#” disappears.
SLX TAG - 0001
READY...
Memo recording
The function of recording a memo in the SFC is called a “scratch pad”.
There are scratch pad 1 and scratch pad 2.
Writing to scratch pad 1
Use the following procedure write data to scratch pad 1.
Here, “01-7 ZERO CHECK” (means “a zero adjustment check was conducted in July
2001”) is entered.
Step
Button
Procedure
SFC screen
1
SHIFT
M
Press [SHIFT] and [
g
] in that order.
- SCR-PADSSCR-PADS is set by
default.
SHIFT-
SLX TAG - 0001
WORKING...
i
MEMO 1
SCR-PADSSCR-PADS
Summary of Contents for SLX 110
Page 1: ...Smart Displacement type Level Transmitter Model SLX 110 120 User s Manual CM2 SLX100 2001...
Page 4: ......
Page 8: ...iv Model SLX 110 120 Smart displacement type level transmitter...
Page 120: ...Operation Azbil Corporation 2 80 Model SLX 110 120 Smart displacement type level transmitter...
Page 150: ...Maintenance Azbil Corporation 3 30 Model SLX 110 120 Smart displacement type level transmitter...
Page 162: ...Azbil Corporation 5 2 Model SLX 110 120 Smart displacement type level transmitter...
Page 163: ......
Page 166: ......
Page 168: ......