Azbil Corporation
Operation
Model SLX 110/120 - Smart displacement type level transmitter 2-63
Engineering unit value
Upper range value/lower range value
Step
Button
Procedure
SFC screen
1
B
CONF
Press [CONF].
SLX CONFIG
FUNCTION CONFIG ?
2
ENTER
( Yes )
NON-VOL
Press [ENTER].
SLX CONFIG
WORKING...
3
The current display format appears.
Example: PV value
DISPLAY TYPE
% (0.0)
4
MENU I
ITEM
DE CONF.
Press [MENU] and select a display
format.
DISPLAY TYPE
ENG.UNIT (4.5 DIG)
5
ENTER
( Yes )
NON-VOL
Press [ENTER].
DISPLAY TYPE
WORKING...
6-1
The current engineering unit value (real
scale) will appear.
EULO (at 0%)
0.0
6-2
H
NEXT
or
L
PREV
To set an upper range value, press
[NEXT] or [PREV] to go to the
engineering unit upper range value
setting screen and set the upper range
value.
EUHI (at 100%)
300.0
7
Enter the desired engineering unit
upper range value using numerical
keys.
Example: Enter value of 100
EULO (at 0%)
100_
8
ENTER
( Yes )
NON-VOL
Press [ENTER].
EULO (at 0%)
ENTERED IN SFC
Summary of Contents for SLX 110
Page 1: ...Smart Displacement type Level Transmitter Model SLX 110 120 User s Manual CM2 SLX100 2001...
Page 4: ......
Page 8: ...iv Model SLX 110 120 Smart displacement type level transmitter...
Page 120: ...Operation Azbil Corporation 2 80 Model SLX 110 120 Smart displacement type level transmitter...
Page 150: ...Maintenance Azbil Corporation 3 30 Model SLX 110 120 Smart displacement type level transmitter...
Page 162: ...Azbil Corporation 5 2 Model SLX 110 120 Smart displacement type level transmitter...
Page 163: ......
Page 166: ......
Page 168: ......