4-11
Chapter 4: Communication-Based Operation
4.4.4 Control configuration
For the device’s dynamic characteristics, the PID parameters are selected based on the
combination of actuator size and gland packing type.
■
Actuator size
Select the actuator size from parameters 0 to 9, A, B, and C (Param 0 to 9, A, B, and C).
(This is selected automatically when auto-setup is executed.)
If auto setup cannot be executed or the desired parameter cannot be set by auto setup,
see the table below to select a PARAM that is suitable for the installed actuator.
Table 4-1. Actuator Size Parameter Table
Actuator Size
(ACTUATOR SIZE)
Operating Speed [s]
Typical Actuator Type
Actuator Capacity
(Typical Value) [cm
3
]
PARAM C
to 0.58
—
—
PARAM B
to 0.8
—
—
PARAM A
to 1.02
—
—
PARAM 1
to 1.5
PSA1, PSK1
600
PARAM 2
to 3
PSA2, HA2
1,400
PARAM 3
to 6.6
PSA3, HA3
2,700
PARAM 4
to 12
PSA4, HA4
6,600
PARAM 5
to 99
VA5
25,300
PARAM 6
to 20
VA6, PSA6
8,100
PARAM 7
to 1.9
RSA1
760
PARAM 8
to 4.3
RSA2
3,800
PARAM 9
to 99
VR3, VR3H
5,800
PARAM 0
—
—
Set individually*
* Consult with Azbil Corporation service personnel.
■
Actuator size configuration procedure
Step
Procedure
1
Select [Device] >> [Setup] >> [Control Configuration] >> [Act. Size/Gland Packing
Type], and check the current setting.
2
Select [Device] >> [Setup] >> [Control Configuration] >> [Change Actuator Size], and
select from parameters 0 to 9, A, B, and C. If parameter 0 has been selected, the gap action
type PID parameters can be set individually. (Parameters 7 to 9 are specifically for the
Azbil Corporation VFR control valve RSA/VR actuator.)
■
Gland packing type
For the hysteresis difference due to friction of the control valve gland packing,
select from [Heavy], [Medium] and [Light]. (This is selected automatically when auto-
setup is executed.) Regarding the types of gland packing, see Table 2 below.
Table 2. Gland Packing Type Parameter Table
Hysteresis* (HYSTERESIS)
Gland packing material example
Heavy (HEAVY)
Graphite packing
Medium (MEDIUM)
Yarn packing
Light (LIGHT)
V type PTFE packing
* This cannot be decided on the basis of material because it depends on the
frictional force of the gland packing.
Summary of Contents for AVP200
Page 30: ......
Page 66: ...2 28...
Page 80: ...4 4 Menu Tree...
Page 120: ...5 16...
Page 128: ...6 8 For models those date of manufacture are before September 2017...
Page 130: ...6 10 For models those date of manufacture are before September 2017...
Page 132: ...6 12 For models those date of manufacture are before September 2017...
Page 136: ...6 16 For models those date of manufacture are after October 2017...
Page 138: ...6 18 For models those date of manufacture are after October 2017...
Page 184: ...Appendix A Specifications A 25...
Page 185: ......
Page 188: ......
Page 190: ......