LIST OF FEATURES
Item
Function
Desired input signal range
Any split-range value can be specified.
Forced fully open/closed
The control valve can be fully closed or opened securely when the desired percentage of input signal
is reached.
Desired flow characteristics
The relationship between input signal and valve travel that is appropriate for the process can be
defined by using a 15-point broken line.
Travel transmission (option)
Valve motion can be reliably monitored by transmitting the valve travel.
FUNCTIONAL SPECIFICATIONS
Item
Specification
Applicable actuator
Pneumatic single and double acting, linear and rotary motion actuator
Input signal
4–20 mA DC (Configurable to any required range for split range.)
Minimum driving current: 3.84 mA
In case of model AVP301 when signal input is less than 3.85 mA, output current will be burnout.
Output signal
4–20 mA DC (Travel transmission)
Input resistance
300 Ω typically / 20 mA DC (Model AVP300/301 Waterproof,Flameproof,ATEX/EAC Intrinsically
safe)
350 Ω typically / 20 mA DC (Model AVP300/301 FM/NEPSI Intrinsically safe)
400 Ω typically / 20 mA DC (Model AVP302)
Lightning protection
Peak value of voltage surge: 12 kV
Peak value of current surge: 1000 A
Flow characteristics
Linear, Equal percentage, Quick opening
Custom user characteristics (15 segments)
Manual operation
Auto/Manual external switch (For single acting actuator only)
Supply air pressure
140 to 700 kPa
Air
consumption
For single acting
actuator
4 L/min (N) or less: with steady supply air pressure of 140 kPa {1.4 kgf/cm
2
} and output of 50 %
5 L/min (N) or less: with steady supply air pressure of 280 kPa {2.8 kgf/cm
2
} and output of 50 %
6 L/min (N) or less: with steady supply air pressure of 500 kPa {5.0 kgf/cm
2
} and output of 50 %
For double acting
actuator
10 L/min (N) or less: with steady supply air pressure of 400 kPa {4.0 kgf/cm
2
}
Output balanced pressure
55±5 % for double acting actuator only
Maximum air
deliver flowrate
For single acting
actuator
110 L/min (N) maximum at 140 kPa {1.4 kgf/cm
2
}
For double acting
actuator
250 L/min (N) maximum at 400 kPa {4.0 kgf/cm
2
}
Air connections
Rc1/4 or 1/4NPT internal thread
Electrical connections
G1/2, 1/2NPT or M20×1.5 internal thread
Ambient temperature limits
−40 to +80°C for general model
TIIS Flameproof: −20 to +55°C
NEPSI Flameproof: −40 to +60°C
KOSHA flameproof
NEPSI Intrinsically safe
Main unit model number “S”: −20 to +55°C
For Ex ia IIC T6: −40 to +40°C
Main unit model number “H”: −40 to +75°C
For Ex ia IIC T5: −40 to +60°C
FM Explosionproof: −40 to +80°C
For Ex ia IIC T4: −40 to +80°C
FM Intrinsically safe: −40 to +80°C
IECEx Flameproof: −40 to +75°C
ATEX Flameproof: −40 to +75°C
INMETRO Flameproof: −40 to +75°C
ATEX Intrinsically safe: −40 to +60°C
EAC Flameproof: −40 to +75°C
EAC Intrinsically safe: −40 to +60°C
CNS Flameproof: −40 to +75°C
Ambient humidity limits
10 to 90 %RH
Finish
Baked acrylic
Color
Dark blue
Material
Cast aluminum
Weight
For single acting
actuator
Without Pressure regulator with filter: 2.5 kg
With Pressure regulator with filter: 3.2 kg
For double acting
actuator
Without Pressure regulator with filter: 2.8 kg
With Pressure regulator with filter: 3.5 kg
Summary of Contents for AVP200
Page 30: ......
Page 66: ...2 28...
Page 80: ...4 4 Menu Tree...
Page 120: ...5 16...
Page 128: ...6 8 For models those date of manufacture are before September 2017...
Page 130: ...6 10 For models those date of manufacture are before September 2017...
Page 132: ...6 12 For models those date of manufacture are before September 2017...
Page 136: ...6 16 For models those date of manufacture are after October 2017...
Page 138: ...6 18 For models those date of manufacture are after October 2017...
Page 184: ...Appendix A Specifications A 25...
Page 185: ......
Page 188: ......
Page 190: ......