3-7
Chapter 3: Operation
3.2.1 Procedure to adjust valve to fully closed position (zero point)
The procedure to adjust the valve to the fully closed position (zero point) is shown
below.
Step
Procedure
1
Input from a controller (constant-current supply) the preset electric current in the
amount that corresponds to the valve being fully closed. (Example: 4 mA)
2
Adjust the fully closed position of the valve by turning the adjustment screw in the
clockwise or counterclockwise direction. See Figure 3-2-1 or Figure 3-2-2 regarding
adjustment direction. (If the forced fully closed function is operating, the valve will not
move. To change the forced fully closed setting, see 4.4.7, “Forced fully open/closed
setting.” The default value is 0.5 %.)
3.2.2 Procedure to adjust valve to fully open position (span point)
The procedure to adjust the valve to the fully open position (span point) is shown
below.
Step
Procedure
1
Input from a controller (constant-current supply) the preset electric current in the
amount that corresponds to the valve being fully open. (Example: 20 mA)
2
Adjust the fully open position of the valve by turning the adjustment screw in the
clockwise or counterclockwise direction. See Figure 3-2-1 or Figure 3-2-2 regarding
adjustment direction.
Note
•
After valve fully open/closed position (zero/span) adjustment, vary the input signal
and confirm that the corresponding position results.
•
After adjustment ends, hold the input signal at 4 mA or higher for 30 seconds so
that the position settings are written to non-volatile memory.
•
If a span adjustment is performed after auto-setup has been executed, the forced
fully open value will be automatically set to −1 % of the overstroke. If necessary,
reconfigure the forced fully open value.
Summary of Contents for AVP200
Page 30: ......
Page 66: ...2 28...
Page 80: ...4 4 Menu Tree...
Page 120: ...5 16...
Page 128: ...6 8 For models those date of manufacture are before September 2017...
Page 130: ...6 10 For models those date of manufacture are before September 2017...
Page 132: ...6 12 For models those date of manufacture are before September 2017...
Page 136: ...6 16 For models those date of manufacture are after October 2017...
Page 138: ...6 18 For models those date of manufacture are after October 2017...
Page 184: ...Appendix A Specifications A 25...
Page 185: ......
Page 188: ......
Page 190: ......