A-2
Azbil Corporation
No. SS2-AVP300-0100
4
Item
Specification
Performance
Accuracy
For 8 mA≤input signal span < 16 mA: ±1 %F.S. (±2.5 % with user-defined flow characteristics)
For 4 mA≤input signal span < 8 mA: ±1.5 %F.S. (Refer to Table 1. Because accuracy varies depending
on the combination of actuator size and travel.)
Travel transmission
accuracy*
±1 %F.S. (±2.5 % with user-defined flow characteristics)
Stroke coverage
14.3 to 100 mm Stroke (Feedback Lever Angle ±4° to ±20°)
Enclosure classification
JIS C0920 watertight, NEMA type 4X, IP66
Approvals
TIIS Flameproof
Ex d IIC T6 X
KOSHA Flameproof
Ex d IIC T6
Flameproof cable gland must be Ex d IIC approved.
FM Explosionproof
Explosionproof: Class I, Division 1, Group A, B, C, D
Dust-ignition: Class II, Division 1, Group E, F, G
Suitable: Class III, Division 1
Flameproof: Class I, Zone 1, AEx d IIC T6 at T
amb
<80°C
NEMA Type 4X
Installation should comply with NEC.
FM Intrinsically safe
Intrinsically safe: Class I, II, III, Division 1, Group A, B, C, D, E, F, G, T4
Intrinsically safe: Class I, Zone 0, AEx ia IIC T4
Nonincendive: Class I, Division 2, Group A, B, C, D, T5
Suitable: Class II, III, Division 2, Groups F, G, T4
NEMA Type 4X, IP66
The barriers should be FM recognized types and comply with the following
conditions as follows:
Input signal line:
12.02≤V
max
≤30 V, I
max
=100 mA, P
max
=1 W, Ci=0 μF, Li=0.22 mH
For travel transmission line:
V
max
=30 V, I
max
=100 mA, P
max
=1 W, Ci=0.07 μF, Li=0.22 mH
Installation should comply with NEC.
ATEX Flameproof
II 2 G Ex db II C T6 Gb −40 °C≤T
amb
≤+75 °C
IEC IP66
Flameproof cable gland must be Ex db IIC approved.
Note: IP66 waterproof and dust-proof performance can be assured by installing
an appropriate cable gland.
ATEX Intrinsically
safe
II 1 G Ex ia IIC T4
II 1 D Ex iaD 20 IP66 T135 °C
IEC IP66
The barriers should be ATEX certified types and comply with the following
condition as follows:
Input circuit (terminals ±IIN)
Ui=30 V, Ii=100 mA, Pi=1 W, Ci=1 nF, Li=0.2 mH
Output circuit (terminals ±IOUT)
Ui=30 V, Ii=100 mA, Pi=1 W, Ci=3 nF, Li=0.2 mH
NEPSI Flameproof
EX d IIC T6 Gb, Ex tD A20 IP66 T85 °C
Flameproof cable gland must be NEPSI Ex d IIC approved.
NEPSI Intrinsically
safe
Ex ia IIC T4-T6
The barriers should be NEPSI certified types and comply with the following
condition as follows:
Input circuit (terminals ±IIN):
Ui=30 V, Ii=95 mA, Pi=0.66 W, Ci=0 μF, Li=0.2 mH
Output circuit (terminals ±IOUT):
Ui=30 V, Ii=95 mA, Pi=0.66 W, Ci=0 μF, Li=0.2 mH
Combination of
NEPSI Flameproof
and Intrinsically safe
When used as NEPSI Flameproof, it complies NEPSI Flameproof approval
as above.
When used as NEPSI Intrinsically safe, it complies NEPSI Intrinsically safe
approval as above.
IECEx Flameproof
Ex db IIC T6 Gb
IEC IP66
Flameproof cable gland must be Ex d IIC approved.
Note: IP66 waterproof and dust-proof performance can be assured by installing
an appropriate cable gland.
Summary of Contents for AVP200
Page 30: ......
Page 66: ...2 28...
Page 80: ...4 4 Menu Tree...
Page 120: ...5 16...
Page 128: ...6 8 For models those date of manufacture are before September 2017...
Page 130: ...6 10 For models those date of manufacture are before September 2017...
Page 132: ...6 12 For models those date of manufacture are before September 2017...
Page 136: ...6 16 For models those date of manufacture are after October 2017...
Page 138: ...6 18 For models those date of manufacture are after October 2017...
Page 184: ...Appendix A Specifications A 25...
Page 185: ......
Page 188: ......
Page 190: ......