Chapter 5: Maintenance and Troubleshooting
5-11
5.7 List of Default Internal Data Values
Item
Contents
Tag number
XXXXXXXX
Output format
ANALOG XMTR
Burnout (fail-safe) indication
DOWN SCALE
Actuator operation
REVERSE
Positioner action
DIRECT
Valve action
DIRECT
Actuator size
PARAM 1
Hysteresis
HEAVY
PID parameter (parameter 0)
P
1.200
I
4.000
D
0.5000
GE
+/−0.000 %
GP
0.7000
GI
4.000
GD
0.5000
Flow characteristics
LINEAR
User-defined flow characteristics data
(Pressure balance type adjustment valve (ADVB/
ADVM) linear characteristics data)
Valve fully closed input (LRV)
4.000 mA
Valve fully open input (URV)
20.00 mA
Forced fully closed input
0.5000 % IIN
Forced fully open input
109.00 % IIN
Digital
output signal
Output signal mode
Single Range
Information volume mode
DE-4 Byte
Failsafe mode
F/S= B/O Hi