4-8
4.4 Device Configuration and Adjustment
In device configuration and adjustment, the configuration and adjustment that are nec-
essary for this device to operate properly are performed. For the HART
®
version, first
set the mode of the device to “Out of service.”
Select [Device] >> [Maintenance] >> [Mode] >> [Mode]. You will be able to change the
mode.
Note
For the HART
®
version, when finished performing adjustment and configuration, set
the mode to “In service.”
4.4.1 Auto-setup
Use auto-setup for the following items.
(1) Zero/span adjustment
(2) Actuator action direction configuration
(3) Input signal LRV and URV configuration
(4) Actuator size selection
(5) Hysteresis difference selection
(6) Travel transmission fail safe selection
Warning
•
During auto-setup, the valve moves from fully open. Take appropriate measures be-
forehand to ensure that the movement of the valve will not cause injury or have an
effect on the process.
Step
Procedure
1
Confirm that the input signal is 4 mA or higher.
2
Select [Device] >> [Setup] >> [Basic Setup] >> [Auto Setup] to execute the method.
3
Following the screen display, execute the operation. The control valve will start to move.
This operation takes about two to three minutes.
4
When the operation ends, “Auto Setup is Completed” is displayed on the screen. When
control via the input signal becomes possible, auto-setup ends.
5
Vary the input signal and check the movement to confirm that adjustment is being
performed appropriately.
Summary of Contents for AVP200
Page 30: ......
Page 66: ...2 28...
Page 80: ...4 4 Menu Tree...
Page 120: ...5 16...
Page 128: ...6 8 For models those date of manufacture are before September 2017...
Page 130: ...6 10 For models those date of manufacture are before September 2017...
Page 132: ...6 12 For models those date of manufacture are before September 2017...
Page 136: ...6 16 For models those date of manufacture are after October 2017...
Page 138: ...6 18 For models those date of manufacture are after October 2017...
Page 184: ...Appendix A Specifications A 25...
Page 185: ......
Page 188: ......
Page 190: ......