Operation manual - EN
www.atmos.eu
EN - 268
ACD03/04
ARU10 Room unit with temperature correction
DESCRIPTION
ARU10 room unit is designed for easy control of the heating circuit,
providing information on the set modes and room temperature and humidity
measurement. It allowes adjusting the required room temperature using
the rotary knob. It alowes changing the (operating) mode using the toggle
button. The ARU10 room unit enables the ACD03/04 electronic controller to optimize the building
heating (water temperature for the given heating circuit).
Technical Data of the Room Unit
Supply voltage: 12 VDC (5,0 VDC ÷ 14,0 VDC)
Max. consumption: 10 mA / 5,0 V (5 mA / 12 V)
Electrical parts protection: IP20
Protection against electric shock: III
Connecting terminals: electric wires of the 0.2 to 0.75 mm
2
cross-section
Communication line: ATMOSNET - cable length max. 200 m
Dimensions (WxHxD): 80x80x44 mm
INFO
- From one ACD 03/04 controller it is possible to power 3 (5) pcs of ARU10 room units.
Environment
Rooms: indoor
Operational temperature: -20 ÷ +50 °C
Storage temperature: -20 ÷ +50 °C
Humidity: 0 to 90 % relative humidity, non-condensing
ASSEMBLY
The ARU10 room unit is intended for fixing assembly on a wall by means of two screws (4x35) and
dowels (6x30) or on an installation box. The access to assembly openings and to the connection block
is possible after removing the front part of the box. It is necessary to pay attention to the flatness of
the base layer to avoid twisting the back wall of the box and poor contact in the connector of the
terminal block.
The room unit is powered by default directly from the ACD03/ACD04 controller (four-line).
ATTENTION
- The person performing the installation and repair of the ACD03/04
electronic controller and accessories must be properly trained and professionally qualified.
All work must be performed in accordance with valid standards and safety regulations!
13. R
oom units
Summary of Contents for ACD 03
Page 1: ...Operation manual EN www atmos eu EN 1 ACD03 04 Operation manual ...
Page 2: ...Operation manual EN www atmos eu ACD03 04 ...
Page 8: ...Operation manual EN www atmos eu EN 8 ACD03 04 ...
Page 265: ...Operation manual EN www atmos eu EN 265 ACD03 04 12 Overview of menus and their parameters ...