Operation manual - EN
www.atmos.eu
EN - 254
ACD03/04
Alarm overview
Function
abbreviation
Description
Cause of alarm
Number Alarm type
Note
AF
Outdoor temperature
interruption
01
0
system
Heating according to AF=P08
System
, or.
AF2
short circuit
01
1
AF2
Outdoor temperature no. 2
interruption
02
0
system
Heating according to AF
short circuit
02
1
WF
Boiler water temperature
interruption
03
0
system
FAN = OFF, BRE = OFF, DKP = ON
short circuit
03
1
KT
Max
exceeded
03
3
logical
WF > P03
Boiler
> 10min
failure to reach KT
Min
03
4
PF = nundefined and Á = active and WF
< P14
Boiler
> 3 hod
AGF
Boiler flue gas temperature
interruption
04
0
system
FAN = OFF, BRE = OFF, DKP = ON
short circuit
04
1
AGF
Max
exceeded
04
2
logical
afetr 30min
WF2
External boiler temperature EK
interruption
05
0
system
EK = OFF, EKP = ON
short circuit
05
1
AGF
Max
exceeded
05
2
logical
SF
DHW tank temperature
interruption
06
0
system
SLP = OFF
short circuit
06
1
failure to reach DHW
request
06
3
logical
po 240 min
SFB
DHW tank no. 2 temperature
interruption
07
0
system
Heating according to SF
short circuit
07
1
SFINT
Inner DHW tank temperature
interruption
08
0
system
short circuit
08
1
failure to reach DHW
request
08
3
logical
po 240 min
SFR
Return temperature from DHW tank
interruption
09
0
system
short circuit
09
1
SME
General alarm
aktivní
10
0
system
RL1
Return temperature Mix-1
interruption
11
0
system
MKP1 = OFF, actuator MK1 = CLOSE
short circuit
11
1
KT
Max
exceeded
11
2
logical
RL2
Return temperature Mix-2
interruption
12
0
system
MKP2 = OFF, actuator MK2 = CLOSE
short circuit
12
1
KT
Max
exceeded
12
2
logical
RL3
Return temperature Mix-3
interruption
13
0
system
MKP3 = OFF, actuator MK3 = CLOSE
short circuit
13
1
KT
Max
exceeded
13
2
logical
RLF
Indirect return control
interruption
14
0
system
RLP = OFF
short circuit
14
1
INFO
Information temperatures
interruption
15
0
system
short circuit
15
1
KVLF
Solar panel temperature
interruption
16
0
system
SOL = OFF
short circuit
16
1
KVLF
Max
exceeded
16
2
logical
KVLF2
Solar panel temperature
interruption
17
0
system
SOL = OFF
short circuit
17
1
KVLF2
Max
exceeded
17
2
logical
KSPF
Solar tank temperature
interruption
18
0
system
SOL = OFF
short circuit
18
1
* alarm numbers are only additional information
10. Setting menu - Alarms
Summary of Contents for ACD 03
Page 1: ...Operation manual EN www atmos eu EN 1 ACD03 04 Operation manual ...
Page 2: ...Operation manual EN www atmos eu ACD03 04 ...
Page 8: ...Operation manual EN www atmos eu EN 8 ACD03 04 ...
Page 265: ...Operation manual EN www atmos eu EN 265 ACD03 04 12 Overview of menus and their parameters ...