ACD03/04
• P13
Heating circuit
parameter - Maximum flow temperature
The parameter allows you to set the maximum temperature of the water flowing into the heating
circuit using the equithermal curve control (MK type mixed circuit).
Factory default setting:
70 °C
Recommended setting:
underfloor heating: 30 - 40 °C
radiator heating: 70 - 80 °C
convector heating with forced airflow: 80 - 90 °C
INFO -
In the case of underfloor heating, the function protects the floor (tiles) against
damage.
• P14
Heating circuit
parameter - Source temperature increase
The parameter is intended to set the temperature difference, by which the energy source (boiler)
must be warmer with respect to the required water temperature flowing into the heating circuit.
Factory default setting:
4 K
• P15
Heating circuit
parameter - Circuit shutdown delay
The parameter is intended to delay the shutdown of the heating circuit (after working mode change,
the heating circuit shutdown, etc.).
It protects the boiler (source) due to its inertia.
Recommended setting:
0 min
- Connection of a boiler with accumulation tank
15 min
- Connection of a boiler without accumulation tank
Factory default setting:
0 min
10. Setting menu - Heating circuit 1 / 2 / 3 / (4)