Operation manual - EN
www.atmos.eu
EN - 170
ACD03/04
Controlled combined boiler (with modification for burner)
connected with accumulation tank
Example 14
- Hydraulic diagram:
67833
6xxxx (FAN +BRE - combi) + x7xxx (DKP+DHW+ACC) + xx8xx (RLA3) + xxx3x (MK2) + xxxx3 (MK1)
Automatic pellet boiler controlled by the controller based on two sensors on the accumulation (buffer)
tank (PF and FPF).
The ACD 03/04 controller allows the burner operation (BRE) to be switched on and off as required
by the operator (for example when cleaning the boiler). It also allows you to switch to manual stoking
operation after removing the burner according to standard boiler functions. It controls the boiler circuit
pump (DKP), temperature of return water to boiler (RLA), two heating circuits (MK1, MK2) and the
tank (boiler) for DHW heating (SLP).
The operation of the boiler fan (FAN) is always controlled from the ACD03/04 controller.
M
M
Max. 60°C
MK1
MK2
MKP2
MKP1
VF1
VF2
SF
AF
WF
Max. 50°C
ATMOS
ACD
2 - 6 bar
10 – 15 °C
ARU30
ARU10
ARU5
22,5 °c
DKP
M
AGF
FAN L
A25
PF
BRE
SLP
RLA3O
RLA3C
VF3
FPF
10. Setting menu - Hydraulics - Hydraulic diagram
Summary of Contents for ACD 03
Page 1: ...Operation manual EN www atmos eu EN 1 ACD03 04 Operation manual ...
Page 2: ...Operation manual EN www atmos eu ACD03 04 ...
Page 8: ...Operation manual EN www atmos eu EN 8 ACD03 04 ...
Page 265: ...Operation manual EN www atmos eu EN 265 ACD03 04 12 Overview of menus and their parameters ...