10. Setting menu - Hydraulics
/F
unction configuration/Domestic water DHW
SFB (SFB2) – additional (second) sensor of tank for DHW heating
(NTC sensor 20 kΩ)
- sensor improves the charging logic of the DHW tank.
The function is especially suitable for a larger DHW tank. The controller maintains the
required (same) DHW temperature in the tank at the level of the SF and SFB sensors (SF2
and SFB2).
SFB
SLP
SF
+P11
TU
V
SFR (SFR2) – return water sensor from tank exchanger for DHW heating
(NTC 20 kΩ
sensor) - the sensor reduces the DHW charging (operation of the SLP pump), if water
flowing from the exchanger when heating the DHW tank is too hot.
SFR
SLP
SF
ANF(H) 5 - switching contact -
allows simple control of the heating circuit in ON / OFF mode.
ANFa (b) –
switching contact
(for terminals - VI1, VI2, VI3, VI4, VI5) - allows easy
control of the heating circuit by any device (potential-free thermostat) in
ON
mode -
switched terminals (e.g. Comfort )
/ OFF -
disconnected terminals (switched off).
ANFHa (b, c ,d, e) –
switching contact
(for terminals - DVI1, DVI2) - allows easy control
of the heating circuit by classic room thermostat (230 V / 50 Hz) in
ON
mode (e.g. Comfort
) /
OFF
(switched off).