Operation manual - EN
www.atmos.eu
EN - 175
ACD03/04
Hydraulic diagram:
16003
Example 16
Hydraulic diagram:
16003
1
xxxx (not controlled boiler) x
6
xxx (DHW+ACC)
xx
0
xx (none)
xxx
0
x (none)
xxxx
3
(MK1)
Boiler:
DC18SP - combined boiler with exhaust fan and wood / pellets burner (not controlled)
Boiler circui
t: -
Accumulation tank:
YES (750 L buffer tank)
Domestic hot water:
YES (e.g. standard tank 160 L)
Heating circuits:
1 mixed equithermal (MK)
Contr
oller
ACD
03/04
OUTPUTS
INPUTS
Communi-
cation
Terminal / Position
Boiler
DHW
Circuit 1
Circuit 2
Circuit 3
66 (67, 68)
62 - 64
53 - 55
40
41
4, 6
5 - 6
7 - 8
9 - 10
15 - 16
23 - 24
L (N, PE)
IN L
+ L
IN L
FAN L
VA
1
VA
2
DKP
SLP
MKP1
MK1 LA
MK1 LB
MKP2
MK2 LA
MK2 LB
VA3 LA
VA4 LB
AF
WF
SF
VF1
VF2
AGF
PF
VI1
VI2
VI3
VI4
VI5
12V
/
A / B / GND
12V
/
A / B / GND
Function
Controller power supply - L
(N, PE)
**
-
-
-
-
-
DHW
pump - SLP
Circuit 1 pump - MKP1
Servo circuit 1 - MK1O
Servo circuit 1 - MK1C
-
-
-
-
-
Outdoor temperature -
AF
Boiler temperature -
WF
DHW
temperature - SF
Circuit 1 temperature -
VF1
-
-
Temperature on the accumulation tank - upper - PF
-
-
-
*
ARU5 room unit
*
-
-
Boiler
Marking of wires in ATMOS boilers and their connection to controller terminals
REG-L
(N, PE)
L-F
AN IN
L-F
AN OUT
L2-OUT
L-M3
L-PUMP
* VI4 and VI5 terminals are best suited for connecting the ARU5 room unit
** Install the terminal only in case of missing L-FAN IN conductor on the boiler electrical harness
Always connect the N and PE wires to the nearest free N and PE terminals
For flue gas sensor and solar panel sensor use the Pt 1000 type (AGF3, VFF00)
For other sensors, use Pt 100 type (KTF20, SF20, AF20)
10. Setting menu - Hydraulics - Hydraulic diagram
Summary of Contents for ACD 03
Page 1: ...Operation manual EN www atmos eu EN 1 ACD03 04 Operation manual ...
Page 2: ...Operation manual EN www atmos eu ACD03 04 ...
Page 8: ...Operation manual EN www atmos eu EN 8 ACD03 04 ...
Page 265: ...Operation manual EN www atmos eu EN 265 ACD03 04 12 Overview of menus and their parameters ...