Operation manual - EN
www.atmos.eu
EN - 208
ACD03/04
• P23
Boiler
parameter - Switching between sources
The parameter is intended to set the method of switching the source from manual heating (stoking)
to automatic heating with burner for DCxxSP(X), DCxxGSP, CxxSP boilers.
Setting options:
1 - manually
– switching from manual heating (stoking)
to automatic heating
with burner
is performed by holding down the button with the hand symbol
for more
than 3 seconds.
2 - automatically
– switching from manual heating (stocking)
to automatic heating
with
burner
always occurs automatically
after wood burns out, when the flue
gas temperature drops below the AGFmin minimum flue gas temperature
defined by
→
P18
Boiler
parameter.
Factory default setting: 1 - manually
INFO
- Operation of the burner (immediate start) depends on the requirement of the heating
system.
• P24
Boiler
parameter - Delayed FAN shutdown
The parameter is used to set the delay of the shutdown (rundown) of the FAN boiler exhaust fan
after switching off the BRE burner.
The rundown time of the boiler fan is set at least as long as the time set in the relevant BRE burner
(A25, A45, A85) - T5 parameter
Factory default setting:
20 min
INFO
- P24
Boiler
parameter is displayed only when the relevant function is activated
→
P21
Boiler
parameter = 2 -
BRE + time
.
• P25
Boiler
parameter - Display AGF
This parameter allows you to switch
On or Off
the display of the AGF flue-gas duct sensor
temperature (flue gas) on the main screen.
Factory default setting: On
INFO -
For boilers with manual stoking, it is not a real flue gas temperature, but information
about the condition of the boiler (flue-gas duct temperature). For boilers with automatic
heating (stoking) with burner (for pellets), the flue gas temperature is displayed according
to the actual location of the AGF flue gas sensor on the boiler or flue-gas duct.
10. Setting menu - Boiler
Summary of Contents for ACD 03
Page 1: ...Operation manual EN www atmos eu EN 1 ACD03 04 Operation manual ...
Page 2: ...Operation manual EN www atmos eu ACD03 04 ...
Page 8: ...Operation manual EN www atmos eu EN 8 ACD03 04 ...
Page 265: ...Operation manual EN www atmos eu EN 265 ACD03 04 12 Overview of menus and their parameters ...