Controlled boiler connected without accumulation tank
Example 3
- Hydraulic diagram:
33033
3
xxxx (controlled boiler) + x
3
xxx (DKP+DHW) + xx
0
xx (-) + xxx
3
x (MK2) + xxxx
3
(MK1)
Boiler controlled by the controller based on the boiler temperature (WF sensor) and flue gas temperature
(AGF sensor).
The ACD 03/04 controller controls boiler operation (fan - FAN / PRESS), the boiler circuit pump (DKP)
(Laddomat/thermoregulation valve), two heating circuits (MK1, MK2) and the tank (boiler) for DHW
heating (SLP).
M
M
Max. 60°C
B
A
MK1
MK2
SLP
MKP2
MKP1
VF1
VF2
SF
AF
WF
Max. 50°C
ATMOS
ACD
2 - 6 bar
10 – 15 °C
ARU30
ARU10
ARU5
22,5 °c
AGF
FAN L
DKP
10. Setting menu - Hydraulics - Hydraulic diagram