Operation manual - EN
www.atmos.eu
EN - 158
ACD03/04
Controlled boiler (GSE) connected
with accumulation tanks (into series)
Example 8
- Hydraulic diagram:
57833
5
xxxx (controlled boiler) + x
7
xxx (DKP+DHW+ACC) + xx
8
xx (RLA3) + xxx
3
x (MK2) + xxxx
3
(MK1)
Boiler controlled by the controller based on the boiler temperature (WF sensor) and flue gas temperature
(AGF sensor).
The ACD 03/04 controller controls boiler operation (fan - FAN / PRESS + servo flap GSE - SEKGS),
the boiler circuit pump (DKP), temperature of return water to boiler (RLA), two heating circuits (MK1,
MK2), charging and discharge of accumulation tanks conected into series.
INFO
- Domestic hot water DHW is solved by nested flow heating in the storage tank with
SFINT sensor (all DHW requirements are maintained, only without the need for a SLP char-
ging pump.
PF2 and PF3 sensors serve only to provide information on the accumulation tank temperature.
M
M
Max. 60 °C
AF
WF
PF
Max. 50°C
ATMOS
ACD
2 - 6 bar
10 – 15 °C
22,5 °c
MK1
MK2
SLP
MKP2
MKP1
VF1
VF2
ARU30
ARU10
ARU5
DKP
RLA3O
RLA3C
VF3
PF2
PF3
AGF
Servo SEKGS
FAN L
M
SFINT
EHP
10. Setting menu - Hydraulics - Hydraulic diagram