Name
Range
Step Default
Description
VT scaling
factor P/S
-
-
-
A relay feedback value; the calculated scaling factor that is the ratio
between the primary voltage and the secondary voltage.
VT scaling
factor p.u. Pri
-
-
-
A relay feedback value; the scaling factor for the primary voltage's per-
unit value.
VT scaling
factor p.u. Sec -
-
-
A relay feedback value; the scaling factor for the secondary voltage's per-
unit value.
U3 VT scaling
factor P/S U0/
SS
-
-
-
A relay feedback value; the scaling factor that is the ratio between the U3
channel's primary and secondary voltages. This setting is only valid if the
"2LL+U3+U4" mode is selected.
U3 scaling
factor p.u. Pri
-
-
-
A relay feedback value for channel U3; the scaling factor for the primary
voltage's per-unit value. This setting is only valid if the "2LL+U3+U4" mode
is selected.
U3 scaling
factor p.u. Sec -
-
-
A relay feedback value for channel U3; the scaling factor for the
secondary voltage's per-unit value. This setting is only valid if the
"2LL+U3+U4" mode is selected.
U4 VT scaling
factor P/S U0/
SS
-
-
-
A relay feedback value; the scaling factor that is the ration between the U4
channel's primary and secondary voltages. This setting is only valid is the
"2LL+U3+U4" mode is selected.
U4 scaling
factor p.u. Pri
-
-
-
A relay feedback value for channel U4; the scaling factor for the primary
voltage's per-unit value. This setting is only valid if the "2LL+U3+U4" mode
is selected.
U4 scaling
factor p.u. Sec -
-
-
A relay feedback value for channel U4; the scaling factor for the
secondary voltage's per-unit value. This setting is only valid if the
"2LL+U3+U4" mode is selected.
Measurements
The following measurements are available in the measured voltage channels.
Table. 5.2.2 - 26. Per-unit voltage measurements.
Name
Unit
Range
Step
Description
Voltage Ux
("UxVolt p.u.")
× U
n
0.00…500.0 0.01
The RMS voltage measurement (in p.u.) from each of the voltage channels.
Voltage Ux
TRMS
("UxVolt TRMS
p.u.")
× U
n
0.00…500.0 0.01
The TRMS voltage (inc. harmonics up to 31
st
) measurement (in p.u.)
from each of the voltage channels.
Table. 5.2.2 - 27. Secondary voltage measurements.
Name
Unit
Range
Step
Description
Secondary voltage
Ux
("Ux Volt sec")
V
0.00…500.0 0.01
The secondary RMS voltage measurement from each of the voltage
channels.
Secondary voltage
Ux TRMS
("UxVolt TRMS
sec")
V
0.00…500.0 0.01
The secondary TRMS voltage (inc. harmonics up to 31
st
) measurement
from each of the voltage channels.
Table. 5.2.2 - 28. Voltage phase angle measurements.
Name
Unit
Range
Step
Description
Ux Angle
deg
0.00…360.00
0.01
The phase angle measurement from each of the four voltage inputs.
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
74