Name
Range
Step
Default
Description
Scaled input
signal
0: Scaling curve 1
(mA)
1: Scaling curve 2
(mA)
2: Scaling curve 3
(mA)
3: Scaling curve 4
(mA)
4: Scaling curve 1
(position)
5: Scaling curve 2
(position)
6: Scaling curve 3
(position)
7: Scaling curve 4
(position)
-
0: Scaling curve
1 (mA)
Selects the scaled input signal.
This setting is only visible when "Scaled input" is the
selected input mode.
Tap position
ind. setting
0: Not selected
1: Set Ok
2: Wrong setting
3: Meas.Quality
Fault.
-
-
Indicates the status of tap position indication settings. A
read-only parameter.
Tap steps
totally
1…70
1
18
Defines the number of steps from minimum to
maximum.
Tap center
location
1…35
1
9
Defines the position of the nominal, non-regulated tap
location.
Tap step
effect
0.01…10.00%
0.01%
1.67%
Defines the effect of a step (in percentage based on the
nominal voltage).
Tap step
voltage effect
0.00…5000.00V
pri
0.01V
pri
0V
pri
Displays the effect of one tap step on the primary
voltage.
Tap maximum
decrease
-140.00…0.00%
0.01%
0%
Displays the maximum voltage decrease from the
nominal position.
Tap maximum
increase
0.00…140.00%
0.01%
0%
Displays the maximum voltage increase from the
nominal position.
Tap control
band
0.00…140.00%
0.01%
0%
Displays the tap changer's control band.
Tap position
indication
1:
Max.mA.max.Pos.
2:
Min.mA.max.Pos
-
1:
Max.mA.max.Pos
Selects the hightest tap position, the maximum or the
minimum value of mA measurement.
This setting is not visible when "BCD coded inputs" or
"Binary coded inputs" is the selected input mode.
mA input low
range
0.000…20.000mA 0.001mA 4.000mA
Sets the minimum tap position measurement value.
This setting is not visible when "BCD coded inputs" or
"Binary coded inputs" is the selected input mode.
mA input high
range
0.010…20.000mA 0.001mA 20.000mA
Sets the maximum tap position measurement value.
This setting is not visible when "BCD coded inputs" or
"Binary coded inputs" is the selected input mode.
Tap step in
mA
0.000…20.000mA 0.001mA 0mA
Sets the effect of one tap step on the mA measurement.
This setting is not visible when "BCD coded inputs" or
"Binary coded inputs" is the selected input mode.
mA input now
(from the
measurement)
0.000…20.000mA 0.001mA -
Displays the mA input measurement value at
the moment.
This setting is visible, when any of the mA inputs is
selected.
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
282