6.1.5 GOOSE
Arcteq relays support both GOOSE publisher and GOOSE subscriber. GOOSE subscriber is enabled
with the "GOOSE subscriber enable" parameter at
Communication
→
Protocols
→
IEC 61850/
GOOSE. The GOOSE inputs are configured using either the local HMI or the AQtivate software.
There are up to 64 GOOSE inputs available for use. Each of the GOOSE inputs also has a
corresponding input quality signal which can also be used in internal logic. The quality is good, when
the input quality is low (that is, when the quality is marked as "0"). The value of the input quality can
increase as a result of a GOOSE time-out or a configuration error, for example. The status and quality
of the various logical input signals can be viewed at the
GOOSE IN status and GOOSE IN quality tabs
at
Control
→
Device I/O
→
Logical signals.
GOOSE input settings
The table below presents the different settings available for all 64 GOOSE inputs.
Table. 6.1.5 - 232. GOOSE input settings.
Name
Range
Step Default
Description
In use
0: No
1: Yes
-
0: No
Enables and disables the GOOSE input in question.
Application ID
("AppID")
0×0…0×3FFF 0×1
0×0
Defines the application ID that will be matched with the publisher's
GOOSE control block.
Configuration
revision
("ConfRev")
1…2
32
-1
1
1
Defines the configuration revision that will be matched with the publisher's
GOOSE control block.
Data index
("DataIdx")
0…99
1
-
Defines the data index of the value in the matched published frame. It is
the status of the GOOSE input.
NextIdx is
quality
0: No
1: Yes
-
0: No
Selects whether or not the next received input is the quality bit of
the GOOSE input.
Data type
0: Boolean
1: Integer
2: Unsigned
3: Floating
point
-
0:
Boolean Selects the data type of the GOOSE input.
Setting the publisher
The configuration of the GOOSE publisher is done using the IEC 61850 tool in AQtivate (
Tools
→
Communication
→
IEC 61850). Refer to AQtivate-200 Instruction manual for more information on how
to set up GOOSE publisher.
6.1.6 IEC 103
IEC 103 is the shortened form of the international standard IEC 60870-5-103. The AQ-200 series units
are able to run as a secondary (slave) station. The IEC 103 protocol can be selected for the serial ports
that are available in the device. A primary (master) station can then communicate with the Arcteq
device and receive information by polling from the slave device. The transfer of disturbance recordings
is not supported.
NO
NOTE
TE: Once the configuration file has been loaded, the IEC 103 map of the relay can be found in the
AQtivate software (
Tools
→
IEC 103 map).
The following table presents the setting parameters for the IEC 103 protocol.
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
342