Name
Range
Step
Default Functions
Description
LV side
nominal
current (pri)
0.01…50 000.00A
0.01A
0.00A
Info
The calculated primary current of the transformer's
LV side primary current.
LV side
nominal
current (sec)
0.01…250.00A
0.01A
0.00A
Info
The calculated primary current of the transformer's
LV side secondary current.
LV CT nom. to
TR nom. factor 0.01…250.00p.u.
0.01p.u. 0.00p.u. Info
The transformer's LV side calculated nominal to
the CT primary rate.
Transformer
nom.
impedance
0.01…250.00
Ω
0.01
Ω
0.00
Ω
Info
The calculated nominal impedance of the
transformer.
Transformer
nom. Zk
0.01…250.00
Ω
0.01
Ω
0.00
Ω
Info
The calculated nominal short-circuit impedance of
the transformer.
Transformer
nom. SC
inductance
0.001…250.000µH 0.01µH
0.000µH Info
The calculated nominal short-circuit inductance of
the transformer.
Transformer
ratio
0.01…250.00
0.01
0.00
Info
The transformer's calculated ratio (= HV/LV).
LV side max.
3ph SC curr.
0.001…500.000kA 0.001kA 0.000kA Info
The calculated maximum three-phase short-circuit
current in the LV poles of the transformer.
LV side 3ph
SC to HV side
0.001…500.000kA 0.001kA 0.000kA Info
Shows how the calculated maximum three-phase
short-circuit current in the LV side is seen in the
HV side.
LV side max.
2ph SC curr.
0.001…500.000kA 0.001kA 0.000kA Info
The calculated maximum two-phase short-circuit
current in the LV poles of the transformer.
LV side 2ph
SC to HV side
0.001...500.000kA
0.001kA 0.000kA Info
Shows how the calculated maximum two-phase
short-circuit current in the LV side is seen in the
HV side.
Table. 5.3.16 - 143. Output signals of the transformer status monitoring function.
Name
Range Step Default
Description
No/Light load
0: Not
active
1:
Active
1
0: Not
active
The signal is active, when the function detects a current below the "No load
current" limit. This signal presents a situation where there is a very light load,
or only one or no side of the transformer is energized.
HV side inrush
detected
0: Not
active
1:
Active
1
0: Not
active
The signal is active, when the detected current rises above the "High
overcurrent" limit in the HV side.
LV side inrush
detected
0: Not
active
1:
Active
1
0: Not
active
The signal is active, when the detected current rises above the "High
overcurrent" limit in the LV side.
Load normal
0: Not
active
1:
Active
1
0: Not
active
The signal is active when the measured current is below the "Nominal
current" but above the "No load current" limit.
Overloading
0: Not
active
1:
Active
1
0: Not
active
The signal is active, when the measured current is between the "Nominal
current" and the "High overcurrent" limits.
Heavy overloading
(HVY overloading)
0: Not
active
1:
Active
1
0: Not
active
The signal is active, when the measured current is above the "High
overcurrent" limit.
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
208