• An object has both Open input
Open input and C
Close input
lose input signals which are used for indicating the
status of the breaker on the HMI and in SCADA. Status can be indicated by any of the
following: digital inputs, logical inputs or outputs.
• A withdrawable object has both In
In and Out
Out inputs. The status can be indicated by any of the
following: digital inputs, logical inputs or outputs.
• Both Ob
Object r
ject read
eadyy and SSynchr
ynchrocheck permission
ocheck permission have status inputs. If either one is used,
the input(s) must be active for the relay to be able to give the "Object Close" command.
• Ob
Object open
ject open and Ob
Object close
ject close signals define which digital output is controlled.
OPERATION SETTINGS
• Br
Break
eaker tra
er travverse time
erse time: determines how long a gap there can be between a status change
from "Open" to "Closed" before an intermittent status is reported by the function.
• Ma
Max close/open command pulse length
x close/open command pulse length: defines the maximum length of "Open" and "Close"
commands. If the status has changed before the maximum pulse length has elapsed, the
pulse is cut short.
• Contr
Control t
ol termina
ermination timeout
tion timeout: If the status of the object does not change during the set time,
an "Open/Close request failed" event is recorded.
• After the set delay, if the controlled object does not respond accordingly, the procedure is
terminated and a fail message is issued.
CONTROL SETTINGS (APPLICATION)
• Ob
Object applic
ject applicaation close
tion close and Ob
Object applic
ject applicaation open
tion open: a signal set to these points can be
used to open and close the object. Controlling the object through this point does not follow
the local/remote status of the relay.
CONTROL SETTINGS (DI)
• A
Access le
ccess levvel f
el for MIMIC
or MIMIC contr
control
ol: determines the access level required to control the
MIMIC (each level has its own password). By default, the access level is set to "Configurator".
• You can use digital inputs to control the object locally or remotely. Remote controlling via the
bus is configured on the protocol level.
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
27