Radiated emissions:
EN 60255-26 Ch. 5.1, CISPR 11
30…1 000 MHz
Immunity
Electrostatic discharge (ESD):
EN 60255-26, IEC 61000-4-2
Air discharge 15 kV
Contact discharge 8 kV
Electrical fast transients (EFT):
EN 60255-26, IEC 61000-4-4
Power supply input 4 kV, 5/50 ns, 5 kHz
Other inputs and outputs 4 kV, 5/50 ns, 5 kHz
Surge:
EN 60255-26, IEC 61000-4-5
Between wires 2 kV, 1.2/50 µs
Between wire and earth 4 kV, 1.2/50 µs
Radiated RF electromagnetic field:
EN 60255-26, IEC 61000-4-3
f = 80….1 000 MHz, 10 V/m
Conducted RF field:
EN 60255-26, IEC 61000-4-6
f = 150 kHz….80 MHz, 10 V (RMS)
Table. 9.3 - 294. Voltage tests.
Dielectric voltage test
EN 60255-27, IEC 60255-5, EN 60255-1
2 kV (AC), 50 Hz, 1 min
Impulse voltage test
EN 60255-27, IEC 60255-5
5 kV, 1.2/50 µs, 0.5 J
Physical environment compatibility
Table. 9.3 - 295. Mechanical tests.
Vibration test
EN 60255-1, EN 60255-27, IEC 60255-21-1 Class 1
2…13.2 Hz, ± 3.5 mm
13.2…100 Hz, ± 1.0 g
Shock and bump test
EN 60255-1,EN 60255-27, IEC 60255-21-2 Class 1
20 g, 1 000 bumps/direction.
Table. 9.3 - 296. Environmental tests.
Damp heat (cyclic)
EN 60255-1, IEC 60068-2-30
Operational: +25…+55 °C, 93…97 % (RH), 12+12h
Dry heat
EN 60255-1, IEC 60068-2-2
Storage: +70 °C, 16 h
Operational: +55 °C, 16 h
Cold test
EN 60255-1, IEC 60068-2-1
Storage: –40 °C, 16 h
Operational: –20 °C, 16 h