Inaccuracy:
- Voltage
- Current
±1.5 %U
SET
±0.5 %I
SET
or ±15 mA (0.10…4.0 × I
SET
)
Operating time
Control pulse min/max and time between
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (U
M
/U
SET
ratio 1.05
→
)
±1.5 % or ±50 ms
Integrated operating time setting:
- Multiplier (k)
0.000…1800.00, setting step 0.005
Inaccuracy:
- IDMT operating time
- IDMT minimum operating time
±1.5 % or ±35 ms
±20 ms
Instant operation time
Start time and instant operation time (trip):
- U
M
/U
SET
ratio 1.05
→
<50 ms
Reset
Reset ratio:
- Voltage
- Current
95/105 % of the pick-up voltage setting
97 % of the pick-up current setting
Reset time setting
Inaccuracy: Reset time
0.010…10.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
9.2.2.2 Setting group selection
Table. 9.2.2.2 - 286. Technical data for the setting group selection function.
Settings and control modes
Setting groups
8 independent, control-prioritized setting groups
Control scale
Common for all installed functions which support setting groups
Control mode
Local
Any digital signal available in the device
Remote
Force change overrule of local controls either from the setting tool, HMI or SCADA
Operation time
Reaction time
<5 ms from receiving the control signal
9.2.2.3 Object control and monitoring
Table. 9.2.2.3 - 287. Technical data for the object control and monitoring function.
Signals
Input signals
Digital inputs
Software signals
Output signals
Close command output
Open command output
Operation time
Breaker traverse time setting
0.02…500.00 s, setting step 0.02 s
Max. close/open command pulse length
0.02…500.00 s, setting step 0.02 s
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
402