Table. 5.2.2 - 33. System primary voltage measurements.
Name
Unit
Range
Step
Description
System
voltage
magnitude
UL12
("System
volt UL12
mag")
V
0.00…1
000000.00 0.01
The primary RMS line-to-line UL12 voltage (measured or calculated). You can also
select the row where the unit for this is kV.
System
voltage
magnitude
UL23
("System
volt UL23
mag")
V
0.00…1
000000.00 0.01
The primary RMS line-to-line UL23 voltage (measured or calculated). You can also
select the row where the unit for this is kV.
System
voltage
magnitude
UL31
("System
volt UL31
mag")
V
0.00…1
000000.00 0.01
The primary RMS line-to-line UL31 voltage (measured or calculated). You can also
select the row where the unit for this is kV.
System
voltage
magnitude
UL1
("System
volt UL1
mag")
V
0.00…1
000000.00 0.01
The primary RMS line-to-neutral UL1 voltage (measured or calculated). You can
also select the row where the unit for this is kV.
System
voltage
magnitude
UL2
("System
volt UL2
mag")
V
0.00…1
000000.00 0.01
The primary RMS line-to-neutral UL2 voltage (measured or calculated). You can
also select the row where the unit for this is kV.
System
voltage
magnitude
UL3
("System
volt UL3
mag")
V
0.00…1
000000.00 0.01
The primary RMS line-to-neutral UL3 voltage (measured or calculated). You can
also select the row where the unit for this is kV.
System
voltage
magnitude
U0
("System
volt U0
mag")
V
0.00…1
000000.00 0.01
The primary RMS zero sequence U0 voltage (measured or calculated). You can also
select the row where the unit for this is kV. There is also a row where the unit is %.
System
voltage
magnitude
U3
("System
volt U3
mag")
V
0.00…1
000000.00 0.01
The primary measured RMS Synchrocheck voltage (SS). This magnitude is
displayed only when the "2LL+U3+U4" mode is selected and both U3 and U4 are in
use. You can also select the row where the unit for this is kV.
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
76