Name
Range
Step
Default
Description
Continue
time
calculation
during
release
time
1: No
2: Yes
-
1: No
Time calculation characteristics selection. If activated, the operating time
counter continues until a set release time has passed even if the pick-up
element is reset.
The user can reset characteristics through the application. The default setting is a 60 ms delay; the
time calculation is held during the release time.
In the release delay option the operating time counter calculates the operating time during the release.
When using this option the function does not trip if the input signal is not re-activated while the release
time count is on-going.
Events and registers
The neutral overvoltage function (abbreviated "NOV" in event block names) generates events and
registers from the status changes in START, TRIP, and BLOCKED. The user can select which event
messages are stored in the main event buffer: ON, OFF, or both. The function offers four (4)
independent stages; the events are segregated for each stage operation.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.3.12 - 120. Event codes.
Event number
Event channel
Event block name
Event code
Description
5952
93
NOV1
0
Start ON
5953
93
NOV1
1
Start OFF
5954
93
NOV1
2
Trip ON
5955
93
NOV1
3
Trip OFF
5956
93
NOV1
4
Block ON
5957
93
NOV1
5
Block OFF
6016
94
NOV2
0
Start ON
6017
94
NOV2
1
Start OFF
6018
94
NOV2
2
Trip ON
6019
94
NOV2
3
Trip OFF
6020
94
NOV2
4
Block ON
6021
94
NOV2
5
Block OFF
6080
95
NOV3
0
Start ON
6081
95
NOV3
1
Start OFF
6082
95
NOV3
2
Trip ON
6083
95
NOV3
3
Trip OFF
6084
95
NOV3
4
Block ON
6085
95
NOV3
5
Block OFF
6144
96
NOV4
0
Start ON
6145
96
NOV4
1
Start OFF
6146
96
NOV4
2
Trip ON
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
185