Name
Range
Step
Default
Description
PQ Quadrant
0: Undefined
1: Q1 Fwd Ind
2: Q2 Rev Cap
3: Q3 Rev Ind
4: Q4 Fwd Cap
-
0:
Undefined Indicates what the power PQ quadrant is at that moment.
VA Quadrant
0: Undefined
1: Q1 Fwd Cap AV
2: Q2 Rev Ind AV
3: Q3 Rev Cap VA
4: Q4 Fwd Ind VA
-
0:
Undefined Indicates what the power VA quadrant is at that moment.
Reset energy
calculators
("Reset 3ph
Energies")
0: -
1: Reset
-
0: -
Resets the memory of the three-phase energy calculators.
Goes automatically back to the "-" state after the reset is
finished.
Phase active
energy
measurement
0: Disabled
1: Enabled
-
0:
Disabled
Enables/disables the active energy per phase
measurement.
Phase reactive
energy
measurement
0: Disabled
1: Enabled
-
0:
Disabled
Enables/disables the reactive energy per phase
measurement.
Phase energies
megas or kilos
0: Mega
1: Kilo
-
0: Mega
Defines whether energy (per phase) is measured with the
prefix 'kilo' (10
3
) or 'mega' (10
6
).
Reset energy
calculators (per
phase)
("Reset E per
phase")
0: -
1: Reset
-
0: -
Resets the memory of the indivisual phase energy
calculator. Goes automatically back to the "-" state after the
reset is finished.
Table. 5.2.3 - 37. Energy Dose Counter 1 settings
Name
Range
Step
Default
Description
Energy
dose
counter
mode
0: Disabled
1: Activated
-
0: Disabled
Enables/disables energy dose counters generally.
Clear pulse
counter
0: -
1: Clear
-
0: -
Resets the "DC 1…4 Pulses sent" counters back to
zero.
DC 1…4
enable
0: Disabled
1: Enabled
-
0: Disabled
Enables/disables the energy dose counter 1…4
individually.
DC 1…4
Input
signal
select
0: 3PH.Fwd.Act.EP
1: 3PH.Rev.Avt.EP
2:
3PH.Fwd.React.EQ.CAP
3: 3PH.Fwd.React.EQ.IND
4:
3PH.Rev.React.EQ.CAP
5: 3PH.Rev.React.EQ.IND
-
0:
3PH.Fwd.Act.EP
Selects whether the energy is active or reactive,
whether the direction of the energy is forward of
reverse, and whether reactive energy is inductive or
capacitive.
DC 1…4
Input
signal
-1 × 10
6
…1 × 10
6
0.01
-
The total amount of energy consumed.
DC 1…4
Pulse
magnitude
0…1800kW/var
0.005kW/
var
1kW/Var
The set pulse size. An energy pulse is given every
time the set magnitude is exceeded.
DC 1…4
Pulse
length
0…1800s
0.005s
1s
The total length of a control pulse.
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
81