Model
COMBIflo
100/300
COMBIflo
150/300
Space heating parameters
Condensing boiler
-
-
Yes
Yes
Low-temperature boiler(1)
-
-
Yes
Yes
B1 boiler
-
-
No
No
Cogeneration space heater
-
-
No
No
Combination boiler
-
-
Yes
Yes
Rate heat output
P
rated
kW
99
147
Useful heat output at rated heat output and high
temperature regime(2)
P
4
kW
91.5
136.8
Useful heat output at 30% of rated heat output and low
temperature regime(1)
P
1
kW
29.9
43.9
Seasonal space heating energy efficiency in active
mode (weighted average of useful efficiency)
n
son
%
96.5
95.8
Seasonal space heating energy efficiency
n
s
%
93
94
Useful heat output at rated heat output and high
temperature regime(2)
n
4
%
87.7
88.0
Useful heat output at 30% of rated heat output and low
temperature regime(1)
n
1
%
98.1
97.2
Auxillary electricity consumption
Full load
elmax
kW
0.285
0.425
Part load
elmin
kW
0.099
0.139
Standby mode
P
SB
kW
0.013
0.014
Other items
Standby heat loss
P
stby
kW
0.140
0.170
Ignition burner power consumption
P
i
gn
kW
0.000
0.000
Annual Energy consumption
Q
HE
GJ
283
419
Sound power level, indoors
L
WA
dB
61
62
Emissions of nitrogen oxides
NO
X
mg/k
Wh
< 40
< 40
Domestic hot water parameters
Declared load profile
3XL
3XL
Daily electricity consumption
Q
elec
kWh
0.755
0.754
Annual electricity consumption
AEC
kWh
166
166
Water heating energy efficiency
n
hw
%
75
75
Daily fuel consumption
Q
fuel
kWh
60.395
60.748
Annual fuel consumption
AFC
GJ
48
48
Weekly fuel consumption with smart controls
Q
fuel, week,
smart
kWh
-
-
Weekly electricity consumption with smart controls
Q
elec, week,
smart
kWh
-
-
Weekly fuel consumption without smart controls
Q
fuel, week
kWh
-
-
Weekly electricity consumtion without smart controls
Q
elec, week
kWh
-
-
Storage volume
V
l
300
300
Mixed water at 40 °C
V40
l
700
Harmonised standards applied
EN: 13203-2
(2) High temperature regime means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet
(1) Low temperature means for condensing boilers 30°C, for low temperature boilers 37°C and for other heaters 50°C
return temperature (at heater inlet)
Specific precautions that shall be taken when the
water heater is assembled, installed or
maintained:
Before any assembly, installation or maintenance the installation
and operation manual has to be read attentively and is followed
Technical Parameters
Summary of Contents for COMBIflo 100/300
Page 9: ...ANDREWS COMBIflo 7 GB 3 1 GENERAL DIMENSIONS CONNECTIONS 3 0 TECHNICAL DATA ...
Page 12: ...ANDREWS COMBIflo 10 GB 3 4 APPLICATION EXAMPLES Single Heating Circuit Simple ...
Page 13: ...ANDREWS COMBIflo 11 GB Single Heating Circuit Immersion DHW Circulation pump ...
Page 16: ...ANDREWS COMBIflo 14 GB Heating Circuit External 0 10V control ...
Page 17: ...ANDREWS COMBIflo 15 GB BMS INTERNET CONNECTIONS ...
Page 18: ...ANDREWS COMBIflo 16 GB 3 5 WIRING DIAGRAMS PCB 1 ...
Page 19: ...ANDREWS COMBIflo 17 GB PCB 2 3 ...