ANDREWS COMBIfl o
30
GB
Code Minimum distance (mm)
B23 fl ue
C13, C33, C53 fl ue
Model
Model
100
150
100
150
A
Directly below an opening, air brick, opening window etc
2500
2500
2500
2500
B
Above an opening, air brick, opening window etc
1,730
2,165
775
1,105
C
Horizontally to an opening, air brick, opening window etc
1,730
2,165
775
1,105
D
Below gutters, soil pipes or drainpipes
200
200
200
200
E
Below eaves
200
200
200
200
F
Below a balcony or car port roof
Not reco
G
Above ground, roof or balcony level
300
300++
300++
300++
H
From vertical drain or soil pipe
150
150
150
150
J
From an internal or external corner
300
300++
300++
300++
K
From a terminal facing a terminal
2,465
3,390
2,465
3,390
L
Vertically from a terminal on the same wall
2,500
2,500
2,500
2,500
M
Horizontally from a terminal on the same wall
1,730
2,165
775
1,105
N
From a surface or a boundary line facing a terminal
2,795
3,855
2,795
3,855
P
From a opening in a carport (e.g. door, windows) into the building
Not reco
Q
Above a pitched roof
410
620
410
620
R
From a roof structure
2,500
2,500
2,500
2,500
S
Above a fl at roof
410
620
410
620
From any other roof fl ue terminal
1,730
2,170
780
1,110
+Not Recommended - Risk assessment required
++ Plume management recommended
Terminals should be so
positioned as to avoid
products of combustion
entering openings into
buildings or other fl ues or vents
4.13 FLUE TERMINAL POSITIONS
Summary of Contents for COMBIflo 100/300
Page 9: ...ANDREWS COMBIflo 7 GB 3 1 GENERAL DIMENSIONS CONNECTIONS 3 0 TECHNICAL DATA ...
Page 12: ...ANDREWS COMBIflo 10 GB 3 4 APPLICATION EXAMPLES Single Heating Circuit Simple ...
Page 13: ...ANDREWS COMBIflo 11 GB Single Heating Circuit Immersion DHW Circulation pump ...
Page 16: ...ANDREWS COMBIflo 14 GB Heating Circuit External 0 10V control ...
Page 17: ...ANDREWS COMBIflo 15 GB BMS INTERNET CONNECTIONS ...
Page 18: ...ANDREWS COMBIflo 16 GB 3 5 WIRING DIAGRAMS PCB 1 ...
Page 19: ...ANDREWS COMBIflo 17 GB PCB 2 3 ...