ANDREWS COMBIfl o
28
GB
4.12 FLUE SYSTEMS & VENTILATION
I
n order to minimise the height of this appliance, the fl ue spigot plate assembly is supplied separately and
will have to be installed before fi tting the fl ue system:
•
Fully insert (approx 50mm) plastic fl ue pipe section (supplied) into fl ue socket (
see below
).
•
Screw metal air collar onto the top of the fl ue socket with the 8 screws (supplied) (see below)
The appliance can be installed using a number of alternative arrangements depending upon the installation
requirements It is delivered with a 130/200mm concentric outlet in the centre. Flue components are ordered
separately as required.
4.12.1 GENERAL REQUIREMENTS
CAUTION
The installer is responsible for ensuring that the right type of fl ue system is used and that the
diameter and length are correct. Only the accessories supplied by Andrews will ensure that the
correct system components are used.
Flue materials must comply with current regulations and standards
This combination heater may not be used in areas where chemical substances are stored or
used. Some propellants, bleaching and cleaning agents disperse explosive vapours and / or
cause accelerated corrosion.
Be aware that this combination heater may be vulnerable to accelerated corrosion from salty air
e.g. coastal installations. Contact Andrews for advise in these cases.
Refer to BS 6644 and IGE UP10 for detailed recommendations on fl ueing requirements
Summary of Contents for COMBIflo 100/300
Page 9: ...ANDREWS COMBIflo 7 GB 3 1 GENERAL DIMENSIONS CONNECTIONS 3 0 TECHNICAL DATA ...
Page 12: ...ANDREWS COMBIflo 10 GB 3 4 APPLICATION EXAMPLES Single Heating Circuit Simple ...
Page 13: ...ANDREWS COMBIflo 11 GB Single Heating Circuit Immersion DHW Circulation pump ...
Page 16: ...ANDREWS COMBIflo 14 GB Heating Circuit External 0 10V control ...
Page 17: ...ANDREWS COMBIflo 15 GB BMS INTERNET CONNECTIONS ...
Page 18: ...ANDREWS COMBIflo 16 GB 3 5 WIRING DIAGRAMS PCB 1 ...
Page 19: ...ANDREWS COMBIflo 17 GB PCB 2 3 ...