6.2.3 LOW LOSS HEADER AND DHW TANK SENSORS (CONT)
Metal slide
The DHW tank sensor is located in a pocket behind the right hand appliance door.
• Remove the bolt holding the right hand door in place and swing open door to reveal sensor location.
• Remove the securing metal slide and withdraw sensor from pocket.
• Unplug connector from loom and remove sensor.
• Replacement is the reverse.
6.2.4 FLUE SENSOR
This is located at the Flue outlet of the heat exchanger.
• Unplug the sensor from the loom.
• Remove sensor by turning anti-clockwise a quarter turn and withdrawing.
• Replacement is the reverse.
6.2.5 AVS37 GUI DISPLAY
•
Remove bolt holding right hand door in place and swing open door to reveal the back of the GUI
•
Unplug the cable from the rear of the GUI
•
Use a small fl at edged screwdriver release the GUI from its opening, by compressing the four plastic
edge clips and gently pulling display out the front of the opening
•
Replacement is reverse