6.6 FAULT CODE TABLE
Fault
Code
Fault Description
Sub
Code
Notes
10
Outside sensor, error
Any
Outside temperature sensor (B9) is faulty or missing. Check sensor
and wiring for operation (a resistor is pre fi tted which has a value
equivalent to 0
O
C. When an outside sensor is installed the pre fi tted
resistor should be removed).
20
Boiler temperature 1, sensor error
Other
Boiler fl ow sensor (B2) is outside normal limits
439
Boiler fl ow sensor (B2) is short-circuit
440
Boiler fl ow sensor (B2) is open-circuit
22
Water pressure 3 too low
Any
Water pressure in primary system is low and requires refi lling to a
minimum of 1.0 bar
26
Common fl ow temperature sensor
error
Any
Check connections or replace faulty sensor located in fl ow pipe work
up stand section (B10)
28
Flue gas temperature, sensor
error
539
543
Flue gas sensor (B8) is short-circuit
540
544
Flue gas sensor (B8) is open-circuit
40
Return temperature 1, sensor
error
Other
Boiler return sensor (B7) is outside normal limits
441
Boiler return sensor (B7) is short-circuit
442
Boiler return sensor (B7) is open-circuit
50
DHW temperature 1, sensor error
Any
Check connections or replace faulty DHW tank sensor (B3)
60
Room temperature 1, sensor error
Any
Check connections or replace faulty room unit (R1)
81
LPB short-circuit or no power
supply
Any
LPB Short circuit or no bus power supply. Check operation of OCI345
modules and cables
82
LPB address collision
Any
LPB address duplicated on another Control PCB - Check address of
all PCB parameter 6600
83
BSB short circuit
Any
No BSB communication or wires shorted - Check operation of room
units and display modules
84
BSB address collision
Any
Two room units have the same allocation address
98
Extension module 1, error
Any
AGU2.5 confi guration error - Check parameters
99
Extension module 2, error
Any
AGU2.5 confi guration error - Check parameters
100
More than one clock time master
Any
Only one device should be set as the time master, check all LMS14s
(parameter 6640) and any OZW672 connected (in case of connection
to an OZW672, this device should be the master)
102
Clock master without power
reserve
Any
The control PCB battery backup for the time clock has been depleted
following the restoration of power to the heater. If this message has
not cleared within 10 minutes of power being turned on, turn the
power off , wait 10 seconds and turn the power on again. This mes-
sage does not prevent the operation of the heater in any way.
105
Maintenance message
Any
Item requiring attention but not preventing heater operation (e.g. 12
Month service due). Check details of message on the heater Front
GUI screen.
Summary of Contents for COMBIflo 100/300
Page 9: ...ANDREWS COMBIflo 7 GB 3 1 GENERAL DIMENSIONS CONNECTIONS 3 0 TECHNICAL DATA ...
Page 12: ...ANDREWS COMBIflo 10 GB 3 4 APPLICATION EXAMPLES Single Heating Circuit Simple ...
Page 13: ...ANDREWS COMBIflo 11 GB Single Heating Circuit Immersion DHW Circulation pump ...
Page 16: ...ANDREWS COMBIflo 14 GB Heating Circuit External 0 10V control ...
Page 17: ...ANDREWS COMBIflo 15 GB BMS INTERNET CONNECTIONS ...
Page 18: ...ANDREWS COMBIflo 16 GB 3 5 WIRING DIAGRAMS PCB 1 ...
Page 19: ...ANDREWS COMBIflo 17 GB PCB 2 3 ...