4.14 MAXIMUM FLUE EQUIVALENT LENGTHS
Permitted Flue Equivalent Length (FEL) for type C
13
, C
33 &
C
53
fl ue
=
18 meters
Permitted Flue Equivalent Length (FEL) for type B
23
fl ue
=
30 meters
Each fl ue accessory such as bends and straight lengths restrict the fl ue system and have a
FEL
which must
be added together to determine the total. Referring to the table above,
select a suitable fl ue system for the
particular installation requirement and then calculate the
FEL
of the system, this must not be greater than that
stated above.
The fl ue duct can discharge either vertically or horizontally by selection of the correct fl ue terminal. The fl ue
pipe can be fi tted with 90 and 45 degree bends as well as extensions.
Example C
33
:
A fl ue system that uses ten straight lengths, three 90° bends, two 45
o
bends and a horizontal
terminal.
10 x 1m straight lengths
10.0
3 x 90° bends
3.0
2 x 45
o
bends
1.0
1 x Horizontal Terminal
1.0
Total
(within 18m limit)
15.0
Example B
23
:
A system that rises from the Heater and uses seven straight lengths, four 45° bends and a
vertical terminal.
12 x 1m straight lengths
12.0
4 x 45° bends
2.0
Vertical Terminal
1.6
Total
(within 30m limit)
15.6
WARNING
Flue type B
23
- The air inlet connection to the appliance must be fi tted with a Debris Guard. Air is
drawn from the room or compartment in which the heater is installed and therefore the room or
compartment
must be ventilated
(see 4.12.1 on P27)
WARNING
Flue type C
53
- The terminals used for the supply of air and for combustion products must not be
installed on opposite walls of a building
When the combustion fl ue system required is longer than 5m, it is recommended that a separate
system to capture excess condensation formed inside the fl ue is fi tted.
Summary of Contents for COMBIflo 100/300
Page 9: ...ANDREWS COMBIflo 7 GB 3 1 GENERAL DIMENSIONS CONNECTIONS 3 0 TECHNICAL DATA ...
Page 12: ...ANDREWS COMBIflo 10 GB 3 4 APPLICATION EXAMPLES Single Heating Circuit Simple ...
Page 13: ...ANDREWS COMBIflo 11 GB Single Heating Circuit Immersion DHW Circulation pump ...
Page 16: ...ANDREWS COMBIflo 14 GB Heating Circuit External 0 10V control ...
Page 17: ...ANDREWS COMBIflo 15 GB BMS INTERNET CONNECTIONS ...
Page 18: ...ANDREWS COMBIflo 16 GB 3 5 WIRING DIAGRAMS PCB 1 ...
Page 19: ...ANDREWS COMBIflo 17 GB PCB 2 3 ...