![andrews COMBIflo 100/300 Installation, Operation And Maintenance Manual Download Page 62](http://html1.mh-extra.com/html/andrews/combiflo-100-300/combiflo-100-300_installation-operation-and-maintenance-manual_2942787062.webp)
ANDREWS COMBIfl o
60
GB
CAUTION
Changing the heat exchanger will require draining of the primary system. It is essential that all the
air is removed from the heat exchanger before the appliance is operated. To not do so may damage
the heat exchanger and invalidate the warranty.
6.2.14 HEAT EXCHANGER
• Drain as much of the primary water as is necessary to ensure the heat exchanger is empty.
• Disconnect all electrical connections to the fl ue sensor, spark generator, fan and gas valve.
• Disconnect the air tube and air control fl ap (see 6.2.11 for details)
• Release both the heat exchanger demountable connections of the fl ow and return pipes, by removing the
metal clips and pulling the pipes downwards.
• Disconnect the condense drain connection by releasing the plastic clip on the top connector.
• Disconnect the gas valve from the venturi by removing the three securing screws
• Remove the whole burner system using the four retaining nuts holding the heat exchanger door to the
body.
Heat exchanger door
screws
Condense
drain clip
Flow / Return Clips
Gas valve screws (x3)
Summary of Contents for COMBIflo 100/300
Page 9: ...ANDREWS COMBIflo 7 GB 3 1 GENERAL DIMENSIONS CONNECTIONS 3 0 TECHNICAL DATA ...
Page 12: ...ANDREWS COMBIflo 10 GB 3 4 APPLICATION EXAMPLES Single Heating Circuit Simple ...
Page 13: ...ANDREWS COMBIflo 11 GB Single Heating Circuit Immersion DHW Circulation pump ...
Page 16: ...ANDREWS COMBIflo 14 GB Heating Circuit External 0 10V control ...
Page 17: ...ANDREWS COMBIflo 15 GB BMS INTERNET CONNECTIONS ...
Page 18: ...ANDREWS COMBIflo 16 GB 3 5 WIRING DIAGRAMS PCB 1 ...
Page 19: ...ANDREWS COMBIflo 17 GB PCB 2 3 ...