ANDREWS COMBIfl o
40
GB
4.19.5 ROOM UNIT SETUP - QAA55
Perform the following to access the room unit parameters:
1. Press the occupancy button (> 3 seconds). The room unit switches to the service level. The fi rst
parameter is selected; the present value blinks.
2. Use the setting knob to set the required parameter.
3. Briefl y press the occupancy button. The next parameter is selected for setting.
4. Exit service level:
- After 8 seconds without activity, the room unit exits the service level automatically.
- Briefl y press the operating mode button.
Parameter
Dis-
play
Function
Used as
ru = 1
The room unit is addressed as RU1 (default setting).
ru = 2
The room unit is addressed as RU2.
ru = 3
The room unit is addressed as RU3.
Direct adjust-
ment
P1 = 1
Automatic storage: (default)
P1 = 2
Save with confi rmation
Operation
Lock
P2 = 0
OFF: All operating elements released (default)
P2 = 1
ON: The following elements are locked:
- Operation changeover heating circuit.
- Readjustment of comfort setpoint.
- Changeover of operating level (occupancy button)
A setpoint readjustment with the knob is adopted either by pressing the operating mode button or with-
out any further confi rmation (time-out).
Summary of Contents for COMBIflo 100/300
Page 9: ...ANDREWS COMBIflo 7 GB 3 1 GENERAL DIMENSIONS CONNECTIONS 3 0 TECHNICAL DATA ...
Page 12: ...ANDREWS COMBIflo 10 GB 3 4 APPLICATION EXAMPLES Single Heating Circuit Simple ...
Page 13: ...ANDREWS COMBIflo 11 GB Single Heating Circuit Immersion DHW Circulation pump ...
Page 16: ...ANDREWS COMBIflo 14 GB Heating Circuit External 0 10V control ...
Page 17: ...ANDREWS COMBIflo 15 GB BMS INTERNET CONNECTIONS ...
Page 18: ...ANDREWS COMBIflo 16 GB 3 5 WIRING DIAGRAMS PCB 1 ...
Page 19: ...ANDREWS COMBIflo 17 GB PCB 2 3 ...