6.6 FAULT CODES LIST (CONTINUED)
Fault
Code
Fault Description
Sub
Code
Notes
110
SLT Lock-out
306 431
432 433
434 435
436 756
Electronic temperature limits exceeded. General overheating issue.
Check for pump operation, trapped air and heat exchanger block-
ages. Monitor temperatures of system to establish problem area.
429 818
Criteria for the safe reset of the error sub code 433 (see above) has
not been met. Allow the boiler to cool further before pressing reset
again
305 412
550 551
754
Overheat protection circuit is open circuit (X18 STB). Check for
mechanical activation of the fl ow or rear heat exchanger temperature
limit switches. Investigate possible overheating issue, before replac-
ing any limit switches.
428 438
817
Maximum Delta T of system exceeded. Check pump operation and
presence of trapped air in the heat exchanger. Flow through heat
exchanger may be restricted.
426 437
815
Flow temperature heat up gradient exceeded. Check pump operation
and presence of trapped air in the heat exchanger. Flow through heat
exchanger may be restricted.
427 816
Criteria for the safe reset of the error sub code 426 (see above) has
not been met. Allow the boiler to cool further before pressing reset
again
420 421
819 820
Heat exchanger return temperature greater than fl ow temperature.
Check that the fl ow and return sensor is operating correctly
419 430
813 814
Flow temperature limit exceeded. Check for overheating issues and
fl ow sensor (B2) performance.
809 810
422 423
Flow temperature reading error. Temperature reading less than 0
O
C
or greater than 124
O
C . Check fl ow sensor (B2) and replace if neces-
sary.
425
812
Return temperature limit exceeded. Check for overheating issues and
return sensor (B7) performance.
424
811
Return temperature reading error. Temperature reading less than 0
O
C
or greater than 124
O
C . Check fl ow sensor (B7) and replace if neces-
sary.
111
Shutdown limit thermostat
Any
Heat exchanger temperatures have been exceeded. Investigate fl ow
speeds and controls to determine causes of temporary fault code.
125
Maximum boiler temperature
exceeded
Any
Flow temperatures have been exceeded. Heater will continue once
temperatures have dropped below maximum allowed limits.
126
DHW charging temperature not
reached
Any
Check operation and heat up times for DHW
127
DHW legionella temperature not
reached
Any
Check operation of legionella function and DHW system. Legionella
setpoint has not been achieved within 48 hours of the function operat-
ing. If using a secondary return sensor, do not set the legionella
setpoint too high, as the heat losses of the pipework may not permit
this to be achieved.
128
Loss of fl ame during operation
Any
Flame lost in heater operation more than 5 times in a 24 hour period.
Check the operation of the ionisation electrode, gas supply, and fl ue
system. View the ionisation current at high and low fl ame. Check CO
2
is correct
130
Flue gas temperature too high
Any
Check causes of high temperatures before operating boiler. Inspect
inside of heat exchanger for dirt build up. Check CO
2
levels at min
and max output.
133
Safety time exceeded
Any
Ignition unsuccessful after 5 attempts within a 24 hour period. Check
ignition and gas circuits for possible faults.
Summary of Contents for COMBIflo 100/300
Page 9: ...ANDREWS COMBIflo 7 GB 3 1 GENERAL DIMENSIONS CONNECTIONS 3 0 TECHNICAL DATA ...
Page 12: ...ANDREWS COMBIflo 10 GB 3 4 APPLICATION EXAMPLES Single Heating Circuit Simple ...
Page 13: ...ANDREWS COMBIflo 11 GB Single Heating Circuit Immersion DHW Circulation pump ...
Page 16: ...ANDREWS COMBIflo 14 GB Heating Circuit External 0 10V control ...
Page 17: ...ANDREWS COMBIflo 15 GB BMS INTERNET CONNECTIONS ...
Page 18: ...ANDREWS COMBIflo 16 GB 3 5 WIRING DIAGRAMS PCB 1 ...
Page 19: ...ANDREWS COMBIflo 17 GB PCB 2 3 ...