Networked Indexer/Driver User Manual
ADVANCED MICRO CONTROLS INC.
76
Command Blocks (continued)
Find Home CCW
Table R7.8 Find Home CCW Command Block
Unused words are ignored by the Networked Driver and can be any value, including parameter values in the
previous command.
Jog CW
Table R7.9 Jog Move CW Command Block
Unused words are ignored by the Networked Driver and can be any value, including parameter values in the
previous command.
EtherNet/IP
or PROFINET
Word
Modbus/TCP
Register
Function
Units
Range
0
1024
16#0040
1
1025
2
1026
Unused
See Note Below
3
1027
Unused
See Note Below
4
1028
Programmed Speed: Upper Word
Steps/Second
Combined value between
the Configured Starting
Speed and 2,999,999
5
1029
Programmed Speed: Lower Word
6
1030
Acceleration
Steps/ms/sec
1 to 5000
7
1031
Deceleration
Steps/ms/sec
1 to 5000
8
1032
Motor Current
0.1 A
SD17060E2: 10 to 60
SD31045E2: 10 to 44
Even numbers only.
9
1033
Acceleration Jerk
0 to 5000
EtherNet/IP
or PROFINET
Word
Modbus/TCP
Register
Function
Units
Range
0
1024
16#0080
1
1025
Bits 7 & 6 must equal “00”
2
1026
Unused
See Note Below
3
1027
Unused
See Note Below
4
1028
Programmed Speed: Upper Word
Steps/Second
Combined value between
the Configured Starting
Speed and 2,999,999
5
1029
Programmed Speed: Lower Word
6
1030
Acceleration
Steps/ms/sec
1 to 5000
7
1031
Deceleration
Steps/ms/sec
1 to 5000
8
1032
Motor Current
0.1 A
SD17060E2: 10 to 60
SD31045E2: 10 to 44
Even numbers only.
9
1033
Acceleration Jerk
0 to 5000