background image

®

®

Process Control and
Automation Solutions
from Elsag Bailey Group

E96-304

Analog Slave Input Module

(IMASI02)

Summary of Contents for infi 90 IMASI02

Page 1: ...Process Control and Automation Solutions from Elsag Bailey Group E96 304 Analog Slave Input Module IMASI02...

Page 2: ...UIPEMENTS LECTRONIQUES SONT SENSIBLES AUX PERTURBATIONS PAR FR QUENCE RADIO DES PR CAUTIONS DEVRONT TRE PRISES LORS DE L UTILISATION DU MAT RIEL DE COMMUNICATION PORTATIF LA PRUDENCE EXIGE QUE LES PR...

Page 3: ...MFP or the Smart Transmitter Ter minal STT to Bailey Controls smart transmitters This instruction explains the slave module features specifica tions and operations It details the procedures you must f...

Page 4: ...l 6 1 through 6 4 Original 7 1 Original 8 1 Original 9 1 Original A 1 through A 3 Original B 1 through B 3 Original When an update is received insert the latest changed pages and dispose of the super...

Page 5: ...Hazard During Maintenance Disconnect power or take precautions to ensure that contact with energized parts is avoided when servicing Special Handling This module uses Electrostatic Sensitive Devices E...

Page 6: ...ion ou prendre les pr cautions pour viter tout contact avec des composants sous tension durant l entretien Precautions de Manutention Ce module contient des composantes sensibles aux decharges electro...

Page 7: ...3 SMART TRANSMITTER COMMUNICATION 2 3 MFP Communication 2 4 STT Terminal Communication 2 4 Smart Transmitter Communication 2 4 Command Buffering During Transmitter Communication Failure 2 4 Data Byte...

Page 8: ...6 2 MODULE PIN CONNECTIONS 6 3 SECTION 7 MAINTENANCE 7 1 INTRODUCTION 7 1 MAINTENANCE SCHEDULE 7 1 SECTION 8 REPAIR REPLACEMENT PROCEDURES 8 1 INTRODUCTION 8 1 MODULE REPAIR REPLACEMENT 8 1 SECTION 9...

Page 9: ...AI05 A 1 A 2 Dipshunts for NTAI05 A 2 A 3 Terminal Assignments for NTAI05 A 3 A 4 Cable Connections for NTAI05 A 3 B 1 Input Circuit for NIAI04 B 1 B 2 Dipswitch Settings for NIAI04 B 2 B 3 Terminal A...

Page 10: ...System The slave also provides a signal path from an Infi 90 operator interface such as Operator Interface Station OIS or Configu ration and Tuning Terminal CTT to the Bailey Controls smart transmitt...

Page 11: ...to the Termination Unit TU or Termination Module TM The terminal blocks for field wiring are on the TU TM Refer to Tables 6 3 through 6 5 The connector on the front of the module is for the STT01 ter...

Page 12: ...connect the module before you apply power This section also presents switch and jumper settings Calibration Presents steps to verify if the ASI module is calibrated Operating Procedures Explains the f...

Page 13: ...RENCE DOCUMENTS NOMENCLATURE The following modules and equipment can be used with an ASI module Document Number Description I E96 201 Multi Function Processor IMMFP01 I E96 202 Multi Function Processo...

Page 14: ...t span 5 VDC for 10 VDC input span Common Mode Rejection 90 dB minimum at 60 Hz Normal Mode Rejection 70 dB minimum at 60 Hz Input Impedance 1 Megohm Environmental Electromagnetic Radio Frequency Inte...

Page 15: ...sing capabilities MMU Module Mounting Unit a card cage that provides electrical and communication sup port for Infi 90 modules MSB Most Significant Bit the bit of a binary number that carries the most...

Page 16: ...figure when you read the module description Note that the digital smart transmitter command signal rides on the analog input signal INPUTS The analog input signal enters the P3 card edge connector on...

Page 17: ...on system start up the MFP does not accept inputs from a smart transmitter channel until the transmitter receives its complete configuration from the ASI Input Circuit Description Input signals go thr...

Page 18: ...ress in FC 132 or FC 133 must be the same as the address set on the slave address dipswitch S1 A D CONVERSION A dual slope analog to digital converter does the A D conver sion It has 14 bit resolution...

Page 19: ...D tag report the input or output report the status get the configuration data Smart Transmitter Communication System start up downloads the smart transmitter configura tions and operating ranges from...

Page 20: ...itter operating parameters should not be changed except through the ASI To prevent changes the ASI sends a security byte at the beginning of each communication The security byte triggers the smart tra...

Page 21: ...e mounting unit MMU backplane A 12 position dipshunt placed in a socket on the MMU backplane connects the bus between the master and slave modules Cable assem blies can extend the bus to six MMUs A ma...

Page 22: ...quire special precautions during shipping and handling Static discharge improper grounding and careless handling can damage these devices To help reduce the chance of dam age follow these procedures 1...

Page 23: ...have an address to communicate with the MFP The ASI can have one of 64 addresses address 0 to 63 on the slave expander bus This address identifies the slave to the master module and must be the same a...

Page 24: ...0 1 2 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 1 0 1 32 33 34 35 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 1 0 1 4 5 6 7 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 0 0 1 1 0 1 0 1 36 37 38 39 1 1 1 1 0 0 0 0...

Page 25: ...P2 and P3 respectively Wiring Install the module in the MMU to connect the slave module to the power 5 15 VDC needed to drive the circuits at P1 It also connects P2 to the slave expander bus for comm...

Page 26: ...I does not have any on board fuses PRE OPERATING ADJUSTMENTS You do not have to adjust the ASI before using Figure 3 2 IMASI02 Cable Connections and Termination TP35742A P1 P1 P3 P1 P3 P1 P2 P2 NKTM01...

Page 27: ...C to the chosen channel 3 Set the MFP to execute mode and monitor the channel in Step 1 4 Adjust R22 until the reading is within 0 1 0 1 is 0 004 Volts 5 Input 3 000 VDC 6 Verify the voltage is within...

Page 28: ...smart device both Function Codes 132 and 133 the ASI performs a check It gets the actual configuration of the smart device and compares it to the configuration from the MFC If these two configuration...

Page 29: ...MFP Function Codes 132 ANALOG INPUT SLAVE and 133 SMART TRANSMITTER DEFINITION To enter smart transmitter commands with the hand held STT smart transmitter terminal plug the terminal into the adapter...

Page 30: ...a on the OIS CTT and Bailey Engineering Work Station The module sum mary display screen contains status reports for each module The module summary display screen shows the status data for specific ASI...

Page 31: ...d Refer to the product instruction manual for smart transmitter infor mation on lockout jumpers Master Module Errors The address set on address switch S1 and in the master mod ule setup data must be t...

Page 32: ...will generate a MISSING SLAVE MODULE error if you fail to connect the slave expander bus between the slave module and the master module Verify that the bus is connected on the MMU back plane NOTE Set...

Page 33: ...SYNC Table 6 5 P3 Input Signal Pin Connections Group A Group B Pin Signal Pin Signal 1 INPUT 1 A INPUT 1 2 INPUT 2 B INPUT 2 3 INPUT 3 C INPUT 3 4 INPUT 4 D INPUT 4 5 INPUT 5 E INPUT 5 6 INPUT 6 F IN...

Page 34: ...to your local Bailey Sales Office MAINTENANCE SCHEDULE Do the tasks in Table 7 1 at the times shown Table 7 1 Maintenance Schedule Task Interval Clean and tighten each power and ground connection Ever...

Page 35: ...n the screws are vertical and the open end of the slots face away from the module 2 Gently slide the module out of the MMU 3 Configure the replacement module switch and jumper set tings Ensure they ar...

Page 36: ...is information ready when you call in to order parts 1 Part description part number and quantity 2 Model and serial numbers 3 Bailey instruction manual number page number and fig ure that describes th...

Page 37: ...10 VDC CONFIGURING INPUTS Figure A 1 shows the NTAI05 dipshunt and the analog signal path from the field device to the ASI module for a termination unit application See Figure A 2 for the dipshunt st...

Page 38: ...rnally Powered 4 20 mA Signal Ended Voltage Differential Voltage Above Applications 4 20 mA 1 5 VDC 0 1 VDC 0 5 VDC 0 10 VDC 10 VDC XU17 NOTES 1 Strap one connects pin one to pin 16 Strap 3 connects p...

Page 39: ...TAI05 8 16 7 6 15 5 4 14 3 2 13 1 TB4 8 12 7 6 11 5 4 10 3 2 9 1 TB3 8 8 7 6 7 5 4 6 3 2 5 1 TB2 8 4 7 6 3 5 4 2 3 2 1 1 TB1 NOT USED TERMINAL NUMBER ANALOG INPUT NUMBER TP35745A NOTES 1 THE DIPSHUNT...

Page 40: ...he values in the figure are actual values from the devices on the module See Figure B 2 for the dipswitch set tings Be sure to recheck the dipswitches before you install the NIAI04 The switches may be...

Page 41: ...Externally Powered Signal Ended Voltage Differential Voltage Above Applications 4 20 mA 1 5 VDC 0 1 VDC 0 5 VDC 0 10 VDC 10 VDC NOTE 1 1 8 represent switch positions on dipswitches S1 S15 where 0 is o...

Page 42: ...signments for NIAI04 1 2 3 5 6 7 8 9 10 11 12 13 14 15 16 17 18 4 19 20 21 22 23 24 25 26 27 28 29 30 31 32 TERMINAL NUMBER ANALOG INPUT NUMBER 15 8 14 6 13 5 12 4 11 3 10 2 9 1 7 TP35749A COMMON 24 V...

Page 43: ...8756 ASIA PACIFIC 152 Beach Road Gateway East 20 04 Singapore 189721 Telephone 65 391 0800 Telefax 65 292 9011 EUROPE AFRICA MIDDLE EAST Via Puccini 2 16154 Genoa Italy Telephone 39 10 6582 943 Telefa...

Reviews: