Maintenance
Replacement of enclosure cover seals
G51--202EN06
5/6
11--2011
© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is
strictly prohibited.
GRID
Preparing and installing static seals
Process for
FKG1XP / XV / XW
The table below gives the steps of replacing cover seals :
Step
Action
Comment
1
Remove
the
damaged
seals.
2
Sand if necessary to re-
move all remaining glue.
3
De--grease using isopropyl
alcohol until all traces of the
adhesive
have
been
removed.
Using a clean rag
4
Bring the ends of the new
seal together, applying a
bevelled cut on both, and
place it.
45
o
5
Assemble the half--covers,
applying
recommended
torques on screws.
Refer to the procedure
“Connection with prepara-
tion of contact surfaces”,
see summary for reference
(...31-50.).
3.2 daNm
Vaseline
HM10--35
1XP / 1XV / 1XW
.
A = x 44 / x36 / x32
Summary of Contents for FKG1X
Page 2: ......
Page 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 75: ...This page is intentionally blank This page is intentionally blank...