GRID
Equipments removal
Procedure
Reinstall the TC, VT’s, capacitors and surge arrestors on the supports
respecting the location marks during the disassembly, using the bolts (A--B---
C--E--F) to refer disassemble procedure and proceed as follows :
D
Reinstall the supports equipped on the top of GCB enclosure.
D
Prepare the electrical contact surfaces (see module “Connection with elec-
trical surfaces preparation”).
D
Reinstall the grounding braid of the VT to the enclosure
D
Reconnect the terminals and check the elementary diagram
(VS......EDD01D).
D
Tightening torque application (see module “Tightening torques”).
ATTENTION :
Respect the specific tightening torque on the VT’s as hereaf-
ter
.
J
:
-- Primary (braide) HM10--20 =
1.5 daNm
-- Primary (braide grounding to the GCB enclosure)
HM8--12 =
0.8 daNm
-- Secondary M6--12 =
0.3 daNm
.
NOTE :
The lenght of the braides shall be respected as initial location
HM8--12
M6--12
x1
x5
Secondary
terminals
Primary
terminal
.
J
H1
H2
HM10--20
1.5daNm
0.3daNm
0.8 daNm
Summary of Contents for FKG1X
Page 2: ......
Page 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 75: ...This page is intentionally blank This page is intentionally blank...