Installation
Filling with SF
6
gas
M32--001EN06
9/10
02--2011
© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is
strictly prohibited.
GRID
Moisture content of SF
6
gas in circuit--breaker
Principle
This measurement is not required, the equipment being provided with
molecular sieves in sufficient quantity to give a dew point of
≤
0
°
C (32
°
F) for
an ambient temperature of 20
°
C (68
°
F), this applies for a unit filled to its
nominal pressure for 2 or 3 months.