GRID
Detail of circuit--breaker maintenance operations
Removing the cover
(if applicable)
During certain operations, removal of the cover is indispensable.
The covers should be placed with enclosures, separately and on a flat surfa-
ce.
Caution
GAS-PRESSURIZED ELEMENTS ARE EXPOSED TO AIR WHEN THE
COVER IS REMOVED.
General condition
of the apparatus
The apparatus should be subjected to visual inspection. If patches of corro-
sion are found begin reconditioning of the affected parts.
The table below gives the process respecting surface finish and protection :
Support
Inspection
Action
Galvanized
steel
Oxidized parts
D
Thorough brushing of oxidized
parts.
D
Degreasing with solvent.
D
Application of a coat of zinc
paint.
Painted
galvanized
steel
or
painted
aluminium
alloy
Light scratches
D
Thorough degreasing with sol-
vent.
D
Application of a coat of lacquer
using a brush.
Deep scratches
or flaking
D
Scouring of paint surface with
emery paper 400.
D
Thorough degreasing with solv-
ent.
D
Application of a coat of primer,
then drying for 24 h.
D
Application of a coat of polyure-
thane lacquer using a brush.
Products used :
D
RUMCOAT EEVA primer by DERIVERY ref. 333103.
D
Polyurethane lacquer 780by DERIVERY, ref. depending on color of equip-
ment.
Continued on next page.
Summary of Contents for FKG1X
Page 2: ......
Page 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 75: ...This page is intentionally blank This page is intentionally blank...