Inverter Settings
86
900-0117-01-00 Rev A
~
Load Shed
performs load management. The Auxiliary output activates when DC (battery) voltage
drops below a certain level. The AUX output controls a larger relay, which turns non-critical loads
on or off to conserve battery power.
This option has a settable DC voltage parameter.
Figure 81
Load Shed
~
Gen Alert
is used as a controller with (with limited functionality) for an AC generator with a remote
start feature. It can start and stop the generator based on DC (battery) voltage levels.
This option has settable DC voltage and time parameters.
Note:
This option does not have the same advantages as the Advanced Generator Start (AGS)
function which is controlled directly by the MATE3. (See page 114.)
Figure 82
Gen Alert
~
Fault
enables the AUX output when the inverter shuts down due to an error condition (see
page 40). It can activate a light or alarm to show that the inverter has failed.
~
Vent Fan
enables the AUX output in response to high DC (battery) voltage. It can run a small fan
to ventilate the battery compartment to eliminate gases that result from battery charging.
This option has settable DC voltage and time parameters.
Figure 83
Vent Fan
Set Points for
Load Shed
:
Enable Voltage:
Sets the low-voltage level at
which the Load Shed function turns on the
AUX output. It remains on for three minutes.
Set Points for
Vent Fan:
Enable Voltage:
Sets the high-voltage level at
which the function turns on the AUX output. It
remains on for one minute.
OFF Delay:
Sets the delay time before the
function turns the AUX output on again.
Set Points for
Gen Alert:
ON Voltage:
Sets the low-voltage level at which the
Gen Alert
function turns on the AUX output.
ON Delay:
Sets the delay time after the
ON Voltage
setting is reached before the AUX output is turned on.
OFF Voltage:
Sets the high-voltage level at which the
Gen Alert
function turns off the AUX output.
OFF Delay:
Sets the delay time after the
OFF Voltage
setting is reached before the AUX output is turned off.
Summary of Contents for OutBack Power MATE3
Page 1: ...MATE3 System Display and Controller Owner s Manual ...
Page 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Page 159: ......