MATE3 Settings
128
900-0117-01-00 Rev A
To enable or disable HBX Mode:
1.
Access the
MATE
menu as shown in Figure 113.
2.
Use the control wheel to select the
High Battery Transfer
menu option.
Press the button in the center of the control wheel to select the menu.
3.
Use the control wheel to change
Enable
to
Disable
.
Press the button in the center of the control wheel to accept the selection.
4.
Use the control wheel to increase or decrease the value next to
Grid Connect
.
Press the button in the center of the control wheel to select the set point.
5.
Use the control wheel to increase or decrease the value next to
Grid Disconnect
.
Press the button in the center of the control wheel to select the set point.
6.
Use the control wheel to increase or decrease the value next to
Grid Connect SOC
.
Press the button in the center of the control wheel to select the set point.
7.
Use the control wheel to increase or decrease the value next to
Grid Disconnect SOC
.
Press the button in the center of the control wheel to select the set point.
Figure 126 MATE High Battery Transfer Screen
Set Points:
Enabled/Disabled
Grid Connect
xx.x VDC
(inverter dependent)
Delay
0 to 240 minutes
Grid Disconnect
xx.x VDC
(inverter dependent)
Delay
0 to 240 minutes
Grid Connect
SOC
10% to 100%
Grid Disconnect SOC
50% to 100%
Summary of Contents for OutBack Power MATE3
Page 1: ...MATE3 System Display and Controller Owner s Manual ...
Page 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Page 159: ......