Operation
48
900-0117-01-00 Rev A
CHARGER Hot Key
The
CHARGER
hot key displays the
Charger Status
screen. The
Charger Status
screen displays the
current charger mode, battery voltage, absorb and float voltage settings and timers. Soft key options
include starting or stopping the charger, which is a global command issued to all inverters in the system.
Other options include starting or the bulk or equalization charge functions, which are global command
issued to all inverters and charge controllers in the system.
NOTE:
The charging information displayed on this screen is for inverters only. Note also that if an inverter
or charge controller has a different charging status from the master inverter, this screen will not display its
status.
Figure 41
CHARGER Hot Key
IMPORTANT:
Equalization should only be performed on certain kinds of batteries under
specific conditions. Pressing the
<Start EQ>
soft key will bring up several
recommendations and confirmations to ensure this function is not started
accidentally.
Soft Key Options:
<Back>
returns to the
Home
screen.
<Bulk Charge>
advances to the
Bulk Charge
screen to start a new charging cycle.
<EQ Charge>
advances to the
Equalize Charge
screen.
<Charger Mode>
advances to the
Charger Mode
screen to enable or disable the charger.
Screen Items:
Battery
displays the uncompensated battery voltage.
Charger Control
displays the mode of the charger.
Absorb
displays the target voltage for the Bulk and
Absorption stages. If the timer to the right of either
item is running, the system is in that charging stage.
Float
display the target voltage for the Float stage.
CHARGER Hot Key
Summary of Contents for OutBack Power MATE3
Page 1: ...MATE3 System Display and Controller Owner s Manual ...
Page 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Page 159: ......