Cool Fan
enables the AUX output when the inverter reaches a high internal temperature. It is
intended to trigger a small external fan for additional cooling. This includes sealed inverter
models which come with a Turbo fan.
~
Divert DC
enables the AUX output to divert excess energy to a DC load, in response to high DC
(battery) voltage. The Auxiliary output controls a larger relay, which allows current to flow to a
dedicated DC load when energized.
This option has settable DC voltage and time parameters.
Figure 84
Divert DC
~
Divert AC
enables the AUX output to divert excess energy from the inverter’s output to an AC
load, in response to high DC (battery) voltage. The Auxiliary output controls a larger relay, which
allows current to flow to a dedicated AC load when energized.
This option has settable DC voltage and time parameters.
Figure 85
Divert AC
~
AC Drop
enables the AUX output whenever the inverter disconnects from an AC source. It can
activate a light (or alarm) to show that the utility grid has failed or that a generator has shut off.
Set Points for
Divert AC:
Enable Voltage:
Sets the high-voltage level at which
the Divert AC function turns on the AUX output. It
remains on as long as the voltage remains above this
set point.
OFF Delay:
Prevents the AUX output from turning on
again for a certain amount of time, even if the voltage
rises above the Enable Voltage set point again. This
prevents nuisance cycling of the
Divert AC
function.
Set Points for
Divert DC:
Enable Voltage:
Sets the high-voltage level at which
the Divert DC function turns on the AUX output. It
remains on as long as the voltage remains above this
set point.
OFF Delay:
Prevents the AUX output from turning on
again for a certain amount of time, even if the voltage
rises above the Enable Voltage set point again. This
prevents nuisance cycling of the
Divert DC
function.
Summary of Contents for OutBack Power MATE3
Page 1: ...MATE3 System Display and Controller Owner s Manual ...
Page 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Page 159: ......