Inverter Settings
900-0117-01-00 Rev A
91
Set Points:
Grid-Tie Enable:
Enables or disables the inverter’s grid-interactive function. If
Y
is selected, the
function is turned on. If
N
is selected, the function is turned off.
Sell Voltage:
Sets the operating point for the grid-interactive function. When a renewable source
raises the batteries above this point, the inverter exports power in order to bring the voltage back
down. (The inverter cannot import AC power to raise the batteries to this level.) This means the Sell
feature only functions when excess DC power is available. (However, if the charger is operating, it can
also sell power using other charger set points. See the inverter
Operator’s Manual
for more details.)
Grid-Tie Window:
Sets the requirements that the utility grid must meet for the grid-interactive
function to work. If the voltage and frequency are within the ranges specified in each selection, the
inverter can sell power. Otherwise, the selling function will not operate. The unit will display a
message in the
Sell Status
menu (see page 46). Two selections are available,
IEEE
and
User
. Specific
settings for each setpoint are listed in the inverter
Operator’s Manual.
~
The
IEEE
selection has narrower settings than the
User
setting.
~
IEEE
is required by most utilities in the United States. (For American models, its voltage and
frequency criteria are preset to the requirements of UL1741 and IEEE 1547.)
Summary of Contents for OutBack Power MATE3
Page 1: ...MATE3 System Display and Controller Owner s Manual ...
Page 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Page 159: ......